S.C. Code Regs. § § 8-1007

Current through Register Vol. 48, No. 11, November 22, 2024
Section 8-1007 - IFGC 505.1.1 Commercial cooking appliances vented by exhaust hoods

Where commercial cooking appliances are vented by means of the Type I or Type II kitchen exhaust hood system that serves such appliances, the exhaust system shall be fan powered and the appliances shall be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating. Where a solenoid valve is installed in the gas piping as part of an interlock system, gas piping shall not be installed to bypass such valve. Dampers shall not be installed in the exhaust system.

Exception: An interlock between the cooking appliance and the exhaust hood system shall not be required for appliances that are of the manually operated type and are factory equipped with standing pilot burner ignition systems.

S.C. Code Regs. § 8-1007

Added by State Register Volume 37, Issue No. 6, eff June 28, 2013; State Register Volume 46, Issue No. 05, eff. 5/27/2022.