Smoke detectors shall be installed in all exit access corridors 30 feet on center in accordance with NFPA 72 and the current building code as listed in Section102.B. No smoke detectors shall be placed within three feet of a HVAC supply or return vent.
S.C. Code Regs. § 61-91.2100.2103