Section 61-91.1800.1801 - Fire Alarms (I)
A. A facility shall include a partial, manual, automatic, supervised fire alarm system. The system shall be arranged to transmit an alarm automatically to a third party by an approved method. The alarm system shall notify by audible and visual alarm all areas and floors of the building. The alarm system shall shut down central recirculating systems and outside air units that serve the area(s) of alarm origination as a minimum.
B. There must be a fire alarm pull station at each required exit and in or near each nurses station.
C. All fire, smoke, heat, sprinkler flow, or manual fire alarming devices or systems must be connected to the main fire alarm system and trigger the system when they are activated.