Section 61-75.2000.2001 - Alarms
A. The Facility shall have an alarm system that includes smoke detection in all main areas and pull stations throughout the building, all supervised by the fire alarm system. The Facility shall ensure the alarm system is arranged to transmit an alarm automatically to a third party by an approved method. The Facility shall ensure the alarm system notifies by audible and visual alarm all areas and floors of the building. The Facility shall ensure the alarm system shuts down central recirculating systems and outside air units that serve the area(s) of alarm origination as a minimum.
B. The Facility shall connect all fire, smoke, heat, sprinkler flow, duct detector, and pull stations to the main fire alarm system and ensure they trigger the system when activated.
C. The Facility shall not have a single or multi-station detector or a private system.

S.C. Code Regs. § 61-75.2000.2001

Added by State Register Volume 46, Issue No. 03, eff. 3/25/2022.