Section 61-125.2000 - FIRE PROTECTION, PREVENTION, AND LIFE SAFETY (I)A. Facilities with six (6) or more licensed beds shall have a partial, manual, automatic, supervised fire alarm system. The facility shall arrange the system to transmit an alarm automatically to a third party. The alarm system shall notify by audible and visual alarm all areas and floors of the building. The alarm system shall shut down central recirculation systems and outside air units that serve the area(s) of alarm origination as a minimum.B. All fire, smoke, heat, sprinkler flow, and manual fire alarming devices must be connected to and activate the main fire alarm system when activated.S.C. Code Regs. § 61-125.2000