C. Testing and Calibration of Meters 1. Gas Meter Accuracy a. Every gas meter, removed from service for any cause, or repaired, shall be tested for accuracy and adjusted, if necessary, to accuracy limits of 100 percent ±1.5 percent before being installed or reinstalled. In addition, the LDC shall replace any parts found to be worn or damaged in any meter that does not pass the accuracy test, and is subject to repair. b. Meters removed from service and/or repaired meters must be subjected to an internal pressure of at least 20 inches water column and checked for the presence of leaks. c. Tin case meters shall be subjected to an internal pressure of at least two (2) pounds per square inch when testing to determine the presence of any leaks. d. New, remanufactured or refurbished meters that are accompanied by a certified test certificate are not required to be tested before installation in the field if the test results on the certificate are within accepted accuracy limits of in § 1.6(C)(1)(a) of this Part. 2. Method of Testing: General Test Requirement For the purpose of determining compliance with § 1.6(C)(1)(a) of this Part, the proof of registration of a displacement meter shall be determined by two tests, one known as the "Check-Rate" test, at a rate of flow at approximately 20% - 40% of the rated capacity of the meter, and one known as the "High-Rate" test, at a rate of flow at approximately 80% - 100% of the rated capacity of the meter. The tests at the two rates of flow, the "Check-Rate" test and the "High-Rate" test shall be comparable to within one (1) percent. If the tests at the two rates of flow do not agree to within one (1) percent, the meter must be repaired to meet the criteria. Both tests must also pass the accuracy test limits of 100 percent ± 1.5 percent as described in § 1.6(C)(1)(a) of this Part. The Division will require additional tests based on extenuating circumstances. All tests to determine the accuracy of any gas service meter shall be made with the appropriate bell, sonic nozzle, or transfer prover or other approved standard meter proving method such as differential testing of rotary meters and field proving of turbine meters.
3. Rotary Meters Rotary meters shall be tested at not less than fifteen percent (15%) of full rated flow. A utility shall not install a rotary meter that is more than one half of one percent (0.5%) fast or more than one and one half percent (1.5%) slow at the points of test.
4. Orifice Meters Orifice meters shall be manufactured and installed in accordance with all guidelines specified in the current edition of ANSI/API 2530 (AGA Report No. 3), Orifice Metering of Natural Gas. Orifice meters shall be tested at not less fifteen percent (15%) of full rated flow. The meters shall not be more than one half percent (0.5%) fast or more than one and one half percent (1.5%) slow at the points of the test.
5. Turbine Meters Turbine meters for which the manufacturer has established minimum spin times, may be spin tested to determine their in-service condition. Turbine meters shall be given a spin test at least once every twelve (12) months unless covered under an approved in-service performance-testing program, or the operator receives a written waiver from the customer not to conduct the test per their decision. Any meter found to have a spin time less than the manufacturer's recommended minimum and which cannot be brought up to the minimum by cleaning and lubrication shall be changed and replaced with an accurate meter. Turbine type meters shall be tested at not less than fifteen percent (15%) of full rated flow. The meters shall not be more than one half percent (0.5%) fast or more than one and one half percent (1.5%) slow at the points of the test.
6. Gas Volume Corrections Gas volume corrections for temperature shall be made in accordance with Charles' law. Gas volume corrections for pressure shall be made in accordance with Boyle's law. Gas volume corrections for supercompressibility shall be made in accordance with either of the following publications of the American Gas Association (AGA):
a. Manual for the Determination of Supercompressibility Factors for Natural Gas, Project NX-19 (1962) (A.G.A. Catalog No. L00340), incorporated above in § 1.1(C) of this Part.b. Compressibility and Supercompressibility for Natural Gas and Other Hydrocarbon Gases, Transmission Measurement Committee Report No. 8 (1992 A.G.A. Catalog), incorporated above in § 1.1(C) of this Part.7. Testing Facilities and Equipment a. Each LDC shall maintain the equipment and facilities necessary for accurately testing meters used for the measuring of gas delivered to its customers, unless arrangements approved by the Division shall have been made to have the testing done elsewhere. The LDC shall maintain this equipment in good condition and correct adjustment so that it can determine the accuracy of any service meter to within one half of one percent (0.5%). The area within the meter shop used for the testing of meters shall be designed so that the meters and meter testing equipment are protected from draft and excessive changes in temperature. b. Accepted good practice. The following publications are considered to be representative of accepted good practice in matters of metering and meter testing: (1) American National Standard for Gas Displacement Meters (500 Cubic Feet per Hour Capacity and Under (Class A)), ANSI B 109.1-2000. (2) American National Standard for Diaphragm Type Gas Displacement Meters (Over 500 Cubic Feet per Hour Capacity (Class B)), ANSI B 109.2-2000. (3) American National Standard for Rotary Type Gas Displacement Meters, ANSI B 109.3-2000. 25 (4) Measurement of Gas Flow by Turbine Meters, ANSI/ASME MFC- 4M-1997 and American Gas Association (AGA) Report 7, Sections 8 and 9. (5) Orifice Metering of Natural Gas and Other Related Hydrocarbon Fluids, ANSI/API 2530-1991.8. Measurement of gas at higher than standard service pressure. a. Pressure-recording equipment. If gas is measured to customers through meters at a pressure greater than standard service pressure, the meters shall be equipped with reliable pressure-volume recording gauges or other devices for accurately determining the quantity of gas that has passed through the meter in accordance with contract or tariff provisions. b. Determination of multiplier. In computing the volume of gas at a given pressure base from a pressure-volume chart, the multiplier shall be obtained by the weighted average method, which consists of determining the average pressure for each indicated unit volume on the chart. c. Fixed pressure factor measurement. If the gas metering pressure can be maintained at a constant level so that it will not vary by more than plus or minus 1.0% of the absolute metering pressure, the quantity of gas corrected for pressure for billing purposes may be determined by multiplying the uncorrected volume by the factor of Metering Pressure Plus Atmospheric Pressure Divided by Base Pressure or by a special index with gearing to perform this calculation. The special index shall meet the specifications of ANSI Standard B109.1, §6.2(1986) or ANSI Standard B109.1, §6.9(1986), incorporated above in § 1.1(D) of this Part. The ability of the regulator to maintain the constant pressure shall be verified at or prior to installation. Verification will be established by the use of a verified pressure-indicating gauge (accuracy: ANSI B40.1 Grade 3A, incorporated above in § 1.1(D) of this Part), or a pressure-recording gauge, at both high and low flow conditions where practicable, but never less than one (1) verification under actual operating conditions. Annual reports of the results of periodic tests will be forwarded to the Division by March 31st for the prior year.9. AMR Device Verification All meters with an AMR device shall be tested to verify the AMR reading is in sync with the meter index. AMR devices will be verified at all meter testing and before installation at a customer's premises.