510 R.I. Code R. 510-RICR-00-00-8.6

Current through December 3, 2024
Section 510-RICR-00-00-8.6 - Chapter 4[CE]

Delete C401.2 Application. And add the following:

C401.2 Application. Commercial buildings projects shall comply with the requirements in sections C403 (Building Envelope Requirements), C403 (Building Mechanical Systems), C404 (Service Water Heating), C405 (Electrical Power and Lighting Systems) and C406 (Tenant Spaces, including C406.1.1) in its entirety. As an alternative, commercial buildings projects shall comply with the energy cost budget method in ASHRAE/IESNA 90.1.

Delete without substitute section C401.2.1 Application to existing building.

Delete Table C402.1.4 and substitute the following

TABLE C402.1.4

OPAQUE THERMAL ENVELOPE ASSEMBLY REQUIREMENTS

CLIMATE ZONE

5

All other

Group R

Roofs

Insulation entirely above deck

U-0.032

U-0.032

Metal buildings

U-0.035

U-0.035

Attic and other

U-0.027

U-00021

Walls, Above Grade

Mass

U-0.090

U-0.80

Metal building

U-0.052

U-0.052

Metal framed

U-0.064

U-0.064

Wood framed and other

U-0.064

U-0.064

Walls, Below Grade

Below-grade walls

C-0.119

C-0.119

Floors

Mass

U-0.074

U-0.064

Joist/Framing

U-0.033

U-0.033

Slab-on Grade Floors

Unheated slabs f

F-0.79/0.64

F-0.79/0.64

Heated slabs

F-0.58

F0.58

Opaque Doors

Swinging Door

U-0.37

U-0.37

Garage Door < 14% Glazing

U-0.31

U-0.31

a. Use opaque assembly U-factors, C-factors, and F-factors from ANSI/ASHRAE/IESNA 90.1 Appendix A shall be permitted, provided the construction complies with the applicable construction details from ANSI/ASHRAE/IESNA 90.1 Appendix A.
b. When heated slabs are placed below-grade, below grade walls must meet the F-factor requirements for heated slabs.
c. The first value is for perimeter the second value is for full slab insulation

Delete Table C402.1.3 and substitute the following:

TABLE C402.1.3

OPAQUE THERMAL ENVELOPE REQUIREMENTS

CLIMATE ZONE

5

ALL OTHERS

GROUP R

Roofs

Insulation entirely Above deck

R-30ci

R-30ci

Metal buildings (with R-5 thermal blocksa,b)

(Assembly descriptions can be found in

ANSI/ASHRAE/IESNA Appendix A.)

(When using R-value compliance method, a thermal spacer block shall be provided, otherwise use the U-factor compliance method in Table C402.1.2.)

R-19 + R-11LS

R-19 + R-11LS

Attic and other

R-38

R-49

Walls, Above Grade

Mass

R-11.4ci

R-13.3 ci

Metal buildingc (When using R-value compliance method, a thermal spacer block shall be provided, otherwise use the U-factor compliance method in Table C402.1.2.)

R-13 + R-13ci

R-13 + R-13ci

Metal framed

R-13 + R-7.5ci

R-13 + R-7.5ci

Wood framed and other

R-13 + R-3.8ci or R-20

R-13 + R-7.5ci or R-20 + R-3.8ci

Walls, Below Grade

Below grade wallc

(R-5.7ci is allowed to be substituted with concrete block walls complying with ASTM C 90, un-grouted or partially grouted at thirty-two inches (32") or less on center vertically and forty-eight inches (48") or less on center horizontally, with un-grouted cores filled with materials having a maximum thermal conductivity of 0.44 Btu-in/h-

R-7.5ci

R-7.5ci

Floors

Mass

R-10ci

R-12.5ci

Joist/framing Steel/(wood)

R-30

R-30

Slab-on-Grade Floors

Unheated Slabs

R-10 for 24" below

R-10 for 24" below

Heated slabs

R-15 for 36" below + R5 Full Slab

R-15 for 36" below +

R5 Full Slab

Opaque doors

Swinging

U -0.37

U -0.37

Roll-up or sliding

R -4.75

R -4.75

For SI:1 inch = 25.4mm.

Ci = Continuous insulation. NR = No requirement.

a. Assembly descriptions can be found in ANSI/ASHRAE/IESNA Appendix A.
b. When using R-value compliance method, a thermal spacer block shall be provided, otherwise use the U-factor compliance method in Table C402.1.2.
c. R-5.7ci is allowed to be substituted with concrete block walls complying with ASTM C 90, ungrouted or partially grouted at thirty-two inches (32") or less on center vertically and forty-eight inches (48") or less on center horizontally, with ungrouted cores filled with materials having a maximum thermal conductivity of 0.44 Btu-in/h-f2 F.
d. Where heated slabs are below grade, below-grade walls shall comply with the exterior insulation requirements for heated slabs.
e. Steel floor joist systems shall be insulated to R-38.

Delete Table C402.4 and substitute the following

TABLE C402.4

BUILDING ENVELOPE REQUIREMENTS: FENESTRATION

CLIMATE ZONE

5

Vertical fenestration

U-factor

Fixed fenestration

0.38

Operable fenestration 0.45

Entrance door

0.77

SHGC

SHGC

S E W

PF<0.2 PF 0.2-0.5 0.38 /0.46 / PF> 0.5 0.61

N

PF <0.2 0.51 PF 0.2-0.5 0.56 PF >.5 0.61

Skylights

U-factor

0.50

SHGC

0.40

Add Exception: #8

C402.5.7: Exception: #8 Where a compliant main entrance is already required such as patio doors intended for seasonal use.

Section C403.2.1 Delete and Substitute:

C403.2.1 Calculation of heating and cooling loads. Design loads shall be determined in accordance with the procedures described in the ANSI/ASHRAE/ACCA Standard 183.

The design loads shall account for the building envelope, lighting, ventilation and occupancy loads based on the projected design.

Heating and cooling loads shall be adjusted to account for load reductions that are achieved when energy recovery systems are utilized in the HVAC system.

Alternatively, design loads shall be determined by an approved equivalent computation procedure, using the design parameters specified in Chapter 3.

Delete C403.7.1 and replace with Demand controlled ventilation (Mandatory)

Demand control ventilation (DCV) shall be provided for spaces larger than five hundred (500) square feet (46.5 m2) and with an average occupant load of twenty-five (25) or more people per one thousand (1,000) square feet (93 m2) of floor area and served by systems with one or more of the following:

TABLE C403.7.4(1)

ENERGY RECOVERY REQUIREMENT

CLIMATE ZONE

PERCENT (%) OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE

>30% AND

<40%

>40% AND <50%

>50% AND <60%

>60% AND <70%

>70% AND <80%

> 80%

DESIGN SUPPLY FAN AIRFLOW RATE (cfm)

5

> 5500

>4500

> 3500

> 2000

> 1000

> 0

403.11.1 Delete and substitute:
C403.11.1 Duct and plenum insulation and sealing (Mandatory). All supply and return air ducts and plenums shall be insulated with a minimum of R-8 insulation when located in unconditioned spaces and a minimum of R-12 insulation when located outside the building. When located within a building envelope assembly, the duct or plenum shall be separated from the building exterior or unconditioned or exempt spaces by a minimum of R-8 insulation.

Exceptions:

1. When located within equipment.
2. When the design temperature difference between the interior and exterior of the duct or plenum does not exceed fifteen degrees Fahrenheit (15° F) (eight degrees Celsius (8° C)).
3. All ducts, air handlers and filter boxes shall be sealed. Joints and seams shall comply with section 603.9 of the International Mechanical Code.

Delete Table C403.5.3.3 and replace with the following Table 403.5.3.3

High-Limit Shutoff Control Setting for Air Economizersb

Device Type

Required High Limit

(Economizer Off When):

Equation

Description

Fixed dry bulb

TOA>70°F

Outdoor air temperature exceeds 70°F

Differential dry bulb

TOA> TRA

Outdoor air temperature exceeds return air temperature

Fixed enthalpy with fixed dry-bulb temperatures

hOA>28Btu/lba or TOA>75°F

Outdoor air temperature exceeds 28 Btu/lb of dry aira or Outdoor air temperature exceeds 75°F

For SI: 1 foot = 305mm, °C = (° F - 32)/1.8, 1 Btu/lb = 2.33 kJ/kg.

a. At altitudes substantially different than sea level, the fixed enthalpy limit shall be set to the enthalpy value at 75°F and 50-percent relative humidity. As an example, at approximately 6,000 feet elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb.

b. Devices with selectable setpoints shall be capable of being set to within 2°F and 2 Btu/lb of the setpoint listed.

Delete without substitute section C407

510 R.I. Code R. 510-RICR-00-00-8.6

Amended effective8/1/2019
Amended effective 2/1/2022