510 R.I. Code R. 510-RICR-00-00-4.10

Current through November 7, 2024
Section 510-RICR-00-00-4.10 - Chapter 13

Add the following new section 1301.2.1:

1301.2.1 Maximum inside fuel oil storage. Where connected to a fuel-oil piping system, the maximum amount of fuel oil allowed inside any building shall be 1,320 gallons and the maximum amount of oil connected to any one (1) appliance shall be 660 gallons. Where the amount of fuel oil stored inside a building exceeds 1,320 gallons the storage area shall be in compliance with the R.I. Fire Prevention Code and the State Building Code.

Add the following new section 1305.8:

1305.8 Fuel Oil Supply and Vent Piping: Fill and vent lines for above ground fuel storage tanks shall be permitted to be a minimum of one and one quarter inch (1 1/4") in diameter for a single storage tank up to 500 gallon capacity.

510 R.I. Code R. 510-RICR-00-00-4.10

Amended effective8/1/2019
Amended effective 2/1/2022