Exception: As modified in Section 904.0 for historical buildings.
Exceptions:
Exceptions:
Exception: Where a single means of egress is permitted by the existing occupancy requirements in NFPA 101, Life Safety Code.
Exceptions:
Exception: Where transoms are permitted by the existing occupancy requirements of NFPA 101, Life Safety Code.
Exception: Corridors within a tenant space that is entirely outside the rehabilitation work area need not comply.
Exception: Where exit enclosure is not required by the fire code.
Exception: Means of egress within a tenant space that is entirely outside the rehabilitation work area need not comply.
Exceptions:
Exception: Means of egress within a tenant space that is entirely outside the rehabilitation work area need not comply.
Exception: Means of egress within a tenant space that is entirely outside the rehabilitation work area need not comply.
Exception: Means of egress within a tenant space that is entirely outside the rehabilitation work area need not comply.
Exception: Means of egress within a tenant space that is entirely outside the rehabilitation work area need not comply.
Exception: Interior finish within a tenant space that is entirely outside the rehabilitation work area need not comply.
Exception: In buildings protected throughout by a fire alarm system installed in accordance with 602.6 or an automatic suppression system in accordance with NFPA 13 or NFPA 13R the following is permitted:
In buildings constructed of other than 3B or 5B construction, where continuity of the shaft enclosure is unfeasible, interior vertical openings other than stairways or other egress components, may be enclosed from floor to ceiling with an approved fire rated assembly.
Exceptions: In buildings protected throughout by a fire alarm system installed in 602.6 or an automatic suppression system in accordance with NFPA 13 or NFPA 13R the following is permitted:
In buildings constructed of other than 3B or 5B construction, where continuity of the shaft enclosure is unfeasible, interior vertical openings other than stairways or other egress components, may be enclosed from floor to ceiling with an approved fire rated assembly.
In apartment buildings that are no more than three (3) stories in height, stairwells may be enclosed with lathe and plaster walls that have been maintained properly. If there is wainscoting applied, the wainscoting shall be coated with a Class A, flame retardant paint.
In non-high-rise apartment buildings that are more than three (3) stories in height, stairwells may be enclosed with lathe and plaster walls that have been maintained properly provided the building is protected throughout by a fire alarm system installed in accordance with 602.6 and the stairwells are protected with an automatic suppression system in accordance with NFPA 13. If there is wainscoting applied, the wainscoting shall be coated with a Class A, flame retardant paint.
In mixed-use buildings with apartments located above, that are no more than three (3) stories in height, stairwells may be enclosed with lathe and plaster walls that have been maintained properly. If there is wainscoting applied, the wainscoting shall be coated with a Class A, flame retardant paint.
In non-high rise mixed use buildings with apartments located above, that are more than three (3) stories in height, stairwells may be enclosed with lathe and plaster walls that have been maintained properly provided the building is protected throughout by a fire alarm system installed in accordance with 602.6 and the stairwells are protected with an automatic suppression system in accordance with NFPA 13. If there is wainscoting applied, the wainscoting shall be coated with a Class A, flame retardant paint.
Exception: Where stairway enclosure is not required for existing occupancies in, Life Safety Code.
Exception: Walls are not required to be continuous through concealed floor spaces.
Exception: In other than high-rise structures, where an adequate water supply for sprinkler protection is not available, alternative protection measures that are acceptable to the authority having jurisdiction shall be permitted. For purposes of this exception, adequate water supply shall mean that the water supply available at the site has sufficient flow capability at a residual pressure of 20 psi (138,000 N/m2) to meet the sprinkler system demand criteria.
Exception: In other than high-rise structures, where an adequate water supply for sprinkler protection is not available the authority having jurisdiction shall be permitted to accept alternative protection. For purposes of this exception, adequate water supply shall mean that the water supply available at the site has sufficient flow capability at a residual pressure of 20 psi (138,000 N/m2) to meet the sprinkler system demand criteria.
Exceptions:
Automatic sprinkler systems required by 602.5 shall be supervised in accordance with NFPA 101 Life Safety Code for new construction and the fire alarm provisions of this code. F
Exceptions:
Exceptions:
Assembly (A-2 through A-5)
Hotels and Motels (R-1)
A fire alarm system as prescribed in R.I. Gen. Laws §23-28.25-4(b), as amended, shall be installed in every hotel. In addition, a visual alarm signal shall be installed in guest rooms specifically designed for persons with disabilities. A rate of rise and one hundred thirty-five degree (135o) to one hundred forty degree (140o) fixed temperature thermodetector and a local single station AC smoke detector shall be installed in every sleeping room.
Exception: Buildings no more than two (2) stories high where each guest room has a direct exit to the outside of the building shall have a fire alarm system as prescribed in R.I. Gen. Laws §23-28.25-4(a), as amended and a local single station AC smoke detector shall be installed in each sleeping room.
Boarding Homes (R-1)
Exception: Buildings with accommodations for fewer than ten (10) persons shall have a fire alarm system as prescribed in R.I. Gen. Laws §23-28.25-4(a), as amended.
Rooming Houses (R-1)
Apartment House (R-2)
Industrial, Mercantile, Business, and Storage Building (F-1, F-2, M, B, S-1, S-2)
Theaters (A-1)
Exceptions:
(Elevator approvals by the Department of Labor and Training.) BFO
Exceptions:
(Boilers over 200,000 BTU require approval by the Department of Labor and Training.)
Exception: Such reduction shall be allowed provided that the structural strength and the stability of the building are not reduced to below the Building Code levels.
Exceptions:
Exceptions:
Voluntary alterations to lateral force resisting systems conducted in accordance with the referenced standards of the Building Code shall be permitted. B
NOTE: Where the section is followed by the letter "B", "F", or "O", the following meaning shall apply:
"B" This means that the Building Official or the Plumbing, Mechanical or Electrical Inspector shall review the plans, issue the permit, inspect the installation, and approve the final certificate.
"F" This means that the Fire Official shall review the plans for approval, the Fire Official and/or the Building Official inspects the installation, and the Fire Official observes the final test and approves the final installation. The Building Official shall issue the permits.
"O" This would indicate another State agency approval and inspection is needed. An explanation will indicate the agency and approvals needed.
510 R.I. Code R. 510-RICR-00-00-20.6