Add the following exception to section M2201.1 Materials.
Exception:
Non-metallic storage tanks shall meet the requirements of UL subject 2258 and shall be installed in accordance with manufacturer's instructions.
Delete section M2201.2 and substitute the following.
The maximum amount of fuel oil stored any above ground or inside of a building shall be one thousand three hundred twenty (1,320) gallons (2,498 L) and the maximum amount of oil connected to any one (1) appliance shall be six hundred sixty (660) gallons. When capacity exceeds six hundred sixty (660) gallons the tanks shall be double walled and sized so that they can be removed from the building without dismantling of the tank.
When an oil-fired heating, appliance is located inside a structure, a remote means of shutting off power to the oil pump and firing circuit in addition to the serviceman's switch shall be provided as follows:
The switch shall be located on a wall mounted between sixty inches (60") and eighty inches (80") above the floor surface and be identified with a red cover plate suitably identified as to its purpose.
510 R.I. Code R. 510-RICR-00-00-2.19
Amended effective 2/1/2022