Section 510-RICR-00-00-2.16 - Chapter 16M1601.4.1 Add the following exceptions to section M1601.4.1 Exceptions:
4. Flexible air ducts shall be permitted to be joined with or without tapes using approved mechanically fastened tension straps or flex-ties installed with a tensioning gun or other similar technologies. M1602.2 Add the following to exception #4 M1602.2.4
Exception #4 continued
Return air shall be permitted to be taken from locations such as a kitchen which is provided its own separate and individual system providing one hundred percent (100%) of the supply air for that space.