510 R.I. Code R. 510-RICR-00-00-1.13

Current through November 7, 2024
Section 510-RICR-00-00-1.13 - Chapter 15: Roof Assemblies and Rooftop Structures

Delete IBC section 1507.2.6 attachment and substitute the following:

1507.2.6 Attachment.

Asphalt strip shingles shall have a minimum of six (6) fasteners per shingle strip.

Exceptions:

1. Where the roof slope exceeds twenty (20) units vertical in twelve (12) units horizontal (20:12), special fastening details may be required by the manufacturer.
2. Fastening systems tested by the manufacturer to one hundred ten (110) MPH shall be permitted to be installed in any wind zone.

510 R.I. Code R. 510-RICR-00-00-1.13

Amended effective8/1/2019
Amended effective 2/1/2022