Current through Register Vol. 54, No. 44, November 2, 2024
Section 5320.81 - Building, physical plant and grounds(a) An LTSR may not house more than 16 residents. One provider who had been licensed/approved to operate an LTSR with bed capacity in excess of 16 prior to January 1, 1993, is exempt from this provision.(b) An LTSR shall have the capacity to allow locks on entrances and exits to preclude elopement of involuntarily committed individuals and to prevent unauthorized entrance. Physical attributes of the facility that are intended to maintain necessary levels of protection shall be as unobtrustive as possible to maintain a home-like environment.(c) The LTSR shall have an adequate supply of hot and cold water piped to each wash basin, bathtub/shower, kitchen sink, commercial dishwasher, and to laundry equipment. Hot water accessible to residents may not exceed 130°F at the outlets.(d) Heating in rooms used by residents shall be maintained at a temperature of not less than 65°F or, when there are residents 65 years of age and older, not less than 70°F.(e) Portable space heaters are prohibited. Space heaters shall be adequately vented and installed with permanent connections and protectors.(f) Steam heat radiators and pipes in rooms and areas used by residents and within reach of residents shall be covered.(g) Fireplaces shall be securely screened when in use.