Section 55.21 - Minimum exits(a) There shall be a minimum of two exits reasonably remote from each other. At least 50% of required exits shall be exit discharge doors, stair towers or ramps.(b) Basements used only for storage or mechanical equipment without any permanent occupancy shall have a minimum of two exit access paths except that the Department may permit a single exit access for basements used only for storage or mechanical equipment without any permanent occupancy of less than 1,000 square feet.(c) Mezzanine levels shall have a minimum of two exit access paths except that the Department may permit a single exit access from mezzanines less than 1,000 square feet or mezzanines used exclusively for storage or mechanical equipment without a permanent occupancy.(d) An individual apartment which occupies more than one floor level shall only be required to have an exit from one floor level.