Current through Register Vol. 54, No. 49, December 7, 2024
Section 51.61 - General requirementsEmergency lighting shall be provided as follows:
(1) Exitways, corridors, stairways, passageways, halls, landings of stairs, exit doors, including angles and intersections, and other means of egress.(2) Rooms used for assembly purposes in excess of 750 square feet.(3) To illuminate exit or directional exit signs.(4) Rooms in which emergency lighting equipment is located.(5) Exterior light over required exit discharge.