34 Pa. Code § 3a.35

Current through Register Vol. 54, No. 50, December 14, 2024
Section 3a.35 - Ladders and runways
(a) Walkways, runways and platforms are required between and on top of boilers, which are more than 8-feet high from the operating floor to afford accessibility for the operation and servicing.
(b) Walkways, runways and platforms must meet the following requirements:
(1) Be constructed of metal.
(2) Be constructed of safety treads, standard grating, or similar material with a minimum clear width of 30 inches.
(3) Be constructed by bolts, welds or rivets.
(4) Be equipped with handrails that are 42-inches high with an intermediate rail and 6-inch toeboard.
(c) A stairway that is a means of access to the walkways, runways or platforms must not exceed an angle of 45°.
(d) A ladder that serves as a means of access to walkways, runways or platforms must be constructed:
(1) Of metal.
(2) So the rungs extend through the side members and are permanently secured to the side rails.
(3) So the front of the rungs have a distance of at least 30 inches from the nearest permanent object on the climbing side of the ladder.
(4) So the back of the rungs have a distance of at least 6 1/2 inches from the nearest permanent object.
(5) So there is a clear width of at least 15 inches from the centerline of the ladder on either side across the front of the ladder.
(e) A welder qualified under Standard Qualification Procedures of the American Welding Society is required for welding a walkway, runway, platform or ladder.
(f) A walkway, runway or platform exceeding 6 feet in length must have at least two means of exit access.

34 Pa. Code § 3a.35