Current through Register Vol. 64, No. 1, January 1, 2025
Section 918-311-0050 - Standards for Electrical Plans ReviewA person performing electrical plan review shall do the following as a minimum:
(1) Load Calculations. Check load calculations for appropriateness, completeness and accuracy.(2) Equipment. Check and determine if the equipment is: (a) Suitable for the environment; and(b) Properly sized and rated to meet the minimum code requirements.(3) Service and Feeder. Check service and feeder installations for code compliance related to: (b) Conduit and box fill;(c) Conductor size and ampacity rating;(g) Service grounding conductor size.Or. Admin. Code § 918-311-0050
BCA 33-1991(Temp), f. & cert. ef. 9-30-91; BCA 44-1991, f. & cert. ef. 12-26-91; BCD 19-1996, f. 9-17-96, cert. ef. 10-1-96; Renumbered from 918-320-0340Stat. Auth.: ORS 479.870
Stats. Implemented: ORS 479.870