Or. Admin. Code § 411-087-0460

Current through Register Vol. 63, No. 12, December 1, 2024
Section 411-087-0460 - Water Supply, Sewage Disposal, and Other Piping Systems
(1) Plumbing System. All interior plumbing systems shall be installed and maintained in conformance with the State Plumbing Code which was current at the time of construction, municipal or county ordinances and to m rules of the Building Codes Division governing the installation of interior supplies in buildings:
(a) The material used for plumbing fixtures shall be of nonabsorbent acid-resistant material;
(b) Hot water heaters and tanks:
(A) The hot water heating equipment shall have sufficient capacity to supply water at sinks, showers, and tubs at 105 to 120 degrees Fahrenheit. Hot water supply in these areas shall not exceed 120 degrees Fahrenheit and not be less than 100 degrees Fahrenheit;
(B) The hot water heating equipment shall have sufficient capacity to provide water in the laundry and dietary areas at a minimum temperature of 160 degrees Fahrenheit;
(C) Storage tank(s) shall be fabricated of corrosion-resistant metal or lined with noncorrosive material.
(c) Drainage systems. Insofar as possible, draining piping shall not be installed within the ceiling nor installed in an exposed location in food preparation centers, food serving facilities, food storage areas, and other critical areas. Special precautions shall be taken to protect these areas from possible leakage or condensation from necessary overhead piping systems;
(d) Nonflammable medical gas systems. If used, nonflammable medical gas system installations shall conform to the requirements of NFPA 99, Chapter 4, 1990 Edition;
(e) Clinical vacuum (suction) systems. If used, clinical vacuum system installations shall be in accordance with the requirements of NFPA 99, Chapter 4, 1990 Edition;
(f) Identification. All piping in the heating, ventilation, air conditioning (HVAC) and service water systems shall be color coded or otherwise marked for easy identification.
(2) Water Supply. Hot and cold water, safe, sanitary and suitable for domestic use, shall be distributed at 20 pounds per square inch pressure or greater to conveniently located taps throughout the building. When the water supply is not obtained from the community water supply system and an independent supply is used, such water supply shall be in compliance with the Health Division Administrative Rules.
(3) Sewage and Wastewater:
(a) All sewage and liquid wastes shall be disposed of in a municipal sewer system if such facilities are available. When a municipal sewer system is not available, sewage and liquid wastes shall be collected, treated, and disposed of in an independent sewer system which conforms to the applicable minimum standards of the Department of Environmental Quality;
(b) All drainage and other arrangements for the disposal of excreta, infectious discharges, institutional and kitchen wastes shall conform to the State Plumbing Code, municipal or county ordinances, and to the rules of the State Health Division and the Department of Environmental Quality.

Or. Admin. Code § 411-087-0460

SSD 22-1991, f. 12-31-91, cert. ef. 1-1-92

Publications: Publications referenced are available from the agency.

Stat. Auth.: ORS 410.070 & 441.055

Stats. Implemented: ORS 441.055 & 441.615