Maximum Feed Concentration = 3.16 x 106 x (Filtrate Detection Limit).
LRV = LOG10(Cf) - LOG10(Cp)
Where:
LRV = log removal value demonstrated during the challenge test;
Cf = the feed concentration measured during the challenge test; and
Cp = the filtrate concentration measured during the challenge test. Equivalent units must be used for the feed and filtrate concentrations. If the challenge particulate is not detected in the filtrate, the term Cp is set equal to the detection limit for the purpose of calculating the LRV. An LRV must be calculated for each membrane module evaluated during the challenge test.
Maximum Feed Concentration = 1 x 104 x (Filtrate Detection Limit).
LRV = LOG10(Cf)-LOG10(Cp).
Where:
LRV = log removal value demonstrated during challenge testing;
Cf = the feed concentration measured during the challenge test; and
Cp = the filtrate concentration measured during the challenge test. In applying this equation, the same units must be used for the feed and filtrate concentrations. If the challenge particulate is not detected in the filtrate, then the term Cp must be set equal to the detection limit.