Okla. Admin. Code § 310:615-5-2

Current through Vol. 42, No. 7, December 16, 2024
Section 310:615-5-2 - Clinical facilities
(a)General-purpose examination room(s). For examinations as may be indicated by narrative program, the center shall have a minimum floor area of 80 square feet, excluding such spaces as vestibule, toilet, closet, and work counter (whether fixed or movable). Arrangement shall permit at least 2'-6' clearance at each side and at the foot of the examination table. A lavatory or sink equipped for hand washing and a counter or shelf space for writing shall be provided.
(b)Treatment room(s). Rooms for minor surgical and cast procedures (if provided) shall have a minimum floor area of 120 square feet, excluding vestibule, toilet, closet, and work counter (whether fixed or movable). The minimum floor dimension shall be 10 feet. A lavatory or sink equipped for hand washing and a counter or shelf space for writing shall be provided.

Okla. Admin. Code § 310:615-5-2

Revoked and reenacted at 9 Ok Reg 2021, eff 6-11-92