Current through Vol. 42, No. 4, November 1, 2024
Section 165:26-2-131 - Fencing(a) Tanks not enclosed in vaults must be enclosed with a chain link fence at least 6 ft. (2m) high. The fence must be separated from the tanks by at least 10 ft (3 m) and must have a gate that is secured against unauthorized entry.(b) The area within the fence must be kept free of vegetation, debris and any other material that is not necessary to the proper operation of the tank and piping system.(c) Tanks are not required to be enclosed within a fence if the property on which the tanks are located already has a perimeter security fence.(d) A fence may not be required if another method effectively restricts access to the tanks.Okla. Admin. Code § 165:26-2-131
Added at 21 Ok Reg 2079, eff 7-1-04; Amended at 23 Ok Reg 144, eff 10-6-05 (emergency); Amended at 23 Ok Reg 2297, eff 7-1-06