[Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:8-44-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:8-1-01 of the Administrative Code.]
DUCT CONSTRUCTION
TABLE 1601.1.1
DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESS FOR SINGLE DWELLING UNITSa
ROUND DUCT DIAMETER (inches) | STATIC PRESSURE | |||
1/2-inch water gage | 1-inch water gage | |||
Thickness (inches) | Thickness (inches) | |||
Galvanized | Aluminum | Galvanized | Aluminum | |
< 12 | 0.013 | 0.018 | 0.013 | 0.018 |
12 to 14 | 0.013 | 0.018 | 0.016 | 0.023 |
15 to 17 | 0.016 | 0.023 | 0.019 | 0.027 |
18 | 0.016 | 0.023 | 0.024 | 0.034 |
19 to 20 | 0.019 | 0.027 | 0.024 | 0.034 |
RECTANGULAR DUCT DIMENSION (inches) | STATIC PRESSURE | |||
1/2-inch water gage | 1-inch water gage | |||
Thickness (inches) | Thickness (inches) | |||
Galvanized | Aluminum | Galvanized | Aluminum | |
[] 8 | 0.013 | 0.018 | 0.013 | 0.018 |
9 to 10 | 0.013 | 0.018 | 0.016 | 0.023 |
11 to 12 | 0.016 | 0.023 | 0.019 | 0.027 |
13 to 16 | 0.019 | 0.027 | 0.019 | 0.027 |
17 to 18 | 0.019 | 0.027 | 0.024 | 0.034 |
19 to 20 | 0.024 | 0.034 | 0.024 | 0.034 |
For SI: 1 inch = 25.4 mm, 1 inch water gage = 249 Pa.
a. Ductwork that exceeds 20 inches by dimension or exceeds a pressure of 1 inch water gage shall be constructed in accordance with SMACNA HVAC Duct Construction Standards-Metal and Flexible.
Exception: Spray application of polyurethane foam to the exterior of ducts in attics and crawl spaces shall be permitted subject to all of the following:
Tapes and mastics used to seal metallic and flexible air ducts and flexible air connectors shall comply with UL 181B and shall be marked "181 B-FX" for pressure-sensitive tape or "181 BM" for mastic. Duct connections to flanges of air distribution system equipment shall be sealed and mechanically fastened. Mechanical fasteners for use with flexible nonmetallic air ducts shall comply with UL 181B and shall be marked 181B-C. Crimp joints for round metallic ducts shall have a contact lap of not less than 1 inch (25 mm) and shall be mechanically fastened by means of not less than three sheet-metal screws or rivets equally spaced around the joint.
Closure systems used to seal all ductwork shall be installed in accordance with the manufacturers' instructions.
Exceptions:
Exception: Plumbing waste cleanouts shall be permitted to be located in unvented crawl spaces that receive conditioned air in accordance with Section 408.3.
RETURN AIR
Exceptions:
Replaces: 4101:8-16-01
Ohio Admin. Code 4101:8-16-01
Five Year Review (FYR) Dates: 07/01/2024
Promulgated Under: 119.03
Statutory Authority: 3781.10(A)(1)
Rule Amplifies: 3781.01, 4740.14, 3791.04, 3781.11, 3781.10, 3781.06
Prior Effective Dates: 01/01/2013