[Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:8-44-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:8-1-01 of the Administrative Code.]
CHAPTER 13
GENERAL MECHANICAL SYSTEM REQUIREMENTS
LABELING OF APPLIANCES
TYPE OF FUEL
APPLIANCE ACCESS
Exceptions:
Exceptions:
CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
Note: "A" equals the required clearance with no protection. "B" equals the reduced clearance permitted in accordance with Table 1306.2. The protection applied to the construction using combustible material shall extend far enough in each direction to make "C" equal to "A."
FIGURE 1306.1
REDUCED CLEARANCE DIAGRAM
TABLE 1306.2
REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTIONa,c,d,e,f,g,h,i,j,k,l
For SI: 1 inch = 25.4 mm, 1 pound per cubic foot = 16.019 kg/m3, °C = [(°F - 32)/ 1.8 ], 1 Btu/(h × ft2× °F/in.) = 0.001442299 (W/cm2× °C/cm).
a. Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing.
b. Clearances shall be measured from the surface of the heat producing appliance or equipment to the outer surface of the combustible material or combustible assembly.
c. Spacers and ties shall be of noncombustible material. Spacers and ties shall not be used directly opposite appliance or connector.
d. Where all clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described. (See Figures 1306.1 and 1306.2.)
e. There shall be not less than 1 inch between clearance reduction systems and combustible walls and ceilings for reduction systems using ventilated air space.
f. If a wall protector is mounted on a single flat wall away from corners, adequate air circulation shall be permitted to be provided by leaving only the bottom and top edges or only the side and top edges open with not less than a 1-inch air gap.
g. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum melting point of 1,500°F.
h. Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu inch per square foot per hour °F or less. Insulation board shall be formed of noncombustible material.
i. There shall be not less than 1 inch between the appliance and the protector. The clearance between the appliance and the combustible surface shall not be reduced below that allowed in this table.
j. All clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable.
k. Listed single-wall connectors shall be permitted to be installed in accordance with the terms of their listing and the manufacturer's instructions.
l. For limitations on clearance reduction for solid-fuel-burning appliances see Section 1306.2.3.
For SI: 1 inch = 25.4 mm.
FIGURE 1306.2
WALL PROTECTOR CLEARANCE REDUCTION SYSTEM
APPLIANCE INSTALLATION
Exception: Elevation of the ignition source is not required for appliances that are listed as flammable-vapor-ignition resistant.
MECHANICAL SYSTEMS INSTALLATION
Exception: Cast-iron piping and galvanized steel piping shall not be required to be protected.
Replaces: 4101:8-13-01
Ohio Admin. Code 4101:8-13-01
Five Year Review (FYR) Dates: 07/01/2024
Promulgated Under: 119.03
Statutory Authority: 3781.10(A)(1)
Rule Amplifies: 3781.01, 4740.14, 3791.04, 3781.11, 3781.10, 3781.06
Prior Effective Dates: 05/27/2006, 01/01/2013