[Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:8-44-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:8-1-01 of the Administrative Code.]
GENERAL
ABOVE-GRADE WALL.
ACCESSIBLE.
ADDITION.
AIR BARRIER.
ALTERATION.
AUTOMATIC.
BASEMENT WALL.
BUILDING.
BUILDING SITE.
BUILDING THERMAL ENVELOPE.
CIRCULATING HOT WATER SYSTEM.
CLIMATE ZONE.
CONDITIONED FLOOR AREA.
CONDITIONED SPACE.
CONTINUOUS AIR BARRIER.
CONTINUOUS INSULATION (ci).
CRAWL SPACE WALL.
CURTAIN WALL.
DEMAND RECIRCULATION WATER SYSTEM.
DUCT.
DUCT SYSTEM.
DWELLING UNIT.
ENERGY ANALYSIS.
ENERGY COST.
ENERGY SIMULATION TOOL.
ERI REFERENCE DESIGN.
EXTERIOR WALL.
FENESTRATION.
Site-built fenestration product.
Skylights.
Vertical fenestration.
HEATED SLAB.
HIGH-EFFICACY LAMPS.
HISTORIC BUILDING.
INFILTRATION.
INSULATED SIDING.
INSULATING SHEATHING.
LABELED.
LISTED.
LOW-VOLTAGE LIGHTING.
MANUAL.
OPAQUE DOOR.
PROPOSED DESIGN.
RATED DESIGN.
READILY ACCESSIBLE.
REPAIR.
REROOFING.
RESIDENTIAL BUILDING.
ROOF ASSEMBLY.
ROOF RECOVER.
ROOF REPAIR.
ROOF REPLACEMENT.
R-VALUE (THERMAL RESISTANCE).
SERVICE WATER HEATING.
SOLAR HEAT GAIN COEFFICIENT (SHGC).
STANDARD REFERENCE DESIGN.
SUNROOM.
THERMAL ISOLATION.
THERMOSTAT.
U-FACTOR (THERMAL TRANSMITTANCE).
VENTILATION.
VENTILATION AIR.
VISIBLE TRANSMITTANCE [VT].
WHOLE HOUSE MECHANICAL VENTILATION SYSTEM.
ZONE.
FIGURE 1101.7
CLIMATE ZONES
TABLE 1101.7
CLIMATE ZONES, MOISTURE REGIMES, AND WARM-HUMID
DESIGNATIONS BY STATE, COUNTY AND TERRITORY
OHIO | ||
4A Adams | 4A Hamilton | 5A Noble |
5A Allen | 5A Hancock | 5A Ottawa |
5A Ashland | 5A Hardin | 5A Paulding |
5A Ashtabula | 5A Harrison | 5A Perry |
5A Athens | 5A Henry | 5A Pickaway |
5A Auglaize | 5A Highland | 4A Pike |
5A Belmont | 5A Hocking | 5A Portage |
4A Brown | 5A Holmes | 5A Preble |
5A Butler | 5A Huron | 5A Putnam |
5A Carroll | 5A Jackson | 5A Richland |
5A Champaign | 5A Jefferson | 5A Ross |
5A Clark | 5A Knox | 5A Sandusky |
4A Clermont | 5A Lake | 4A Scioto |
5A Clinton | 4A Lawrence | 5A Seneca |
5A Columbiana | 5A Licking | 5A Shelby |
5A Coshocton | 5A Logan | 5A Stark |
5A Crawford | 5A Lorain | 5A Summit |
5A Cuyahoga | 5A Lucas | 5A Trumbull |
5A Darke | 5A Madison | 5A Tuscarawas |
5A Defiance | 5A Mahoning | 5A Union |
5A Delaware | 5A Marion | 5A Van Wert |
5A Erie | 5A Medina | 5A Vinton |
5A Fairfield | 5A Meigs | 5A Warren |
5A Fayette | 5A Mercer | 4A Washington |
5A Franklin | 5A Miami | 5A Wayne |
5A Fulton | 5A Monroe | 5A Williams |
4A Gallia | 5A Montgomery | 5A Wood |
5A Geauga | 5A Morgan | 5A Wyandot |
5A Greene | 5A Morrow | |
5A Guernsey | 5A Muskingum |
Key: A - Moist.
TABLE 1101.7.2(1)
INTERNATIONAL CLIMATE ZONE DEFINITIONS
Deleted.
TABLE 1101.7.2(2)
INTERNATIONAL CLIMATE ZONE DEFINITIONS
Deleted.
Exception: For roof insulation installed above the deck, the R-value shall be labeled as required by the material standards specified in Table 906.2.
Exception: Where required, garage door U-factors shall be determined in accordance with either NFRC 100 or ANSI/DASMA 105.
U-factors shall be determined by an accredited, independent laboratory, and labeled and certified by the manufacturer.
Products lacking such a labeled U-factor shall be assigned a default U-factor from Table 1101.10.3(1) or 1101.10.3(2). The solar heat gain coefficient (SHGC) and visible transmittance (VT) of glazed fenestration products such as windows, glazed doors and skylights shall be determined in accordance with NFRC 200 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled SHGC or VT shall be assigned a default SHGC or VT from Table 1101.10.3(3).
TABLE 1101.10.3(1)
DEFAULT GLAZED WINDOW, GLASS DOOR AND SKYLIGHT U-FACTORS
FRAME TYPE | WINDOW AND GLASS DOOR | SKYLIGHT | ||
Single pane | Double pane | Single | Double | |
Metal | 1.20 | 0.80 | 2.00 | 1.30 |
Metal with Thermal Break | 1.10 | 0.65 | 1.90 | 1.10 |
Nonmetal or Metal Clad | 0.95 | 0.55 | 1.75 | 1.05 |
Glazed Block | 0.60 |
TABLE 1101.10.3(2)
DEFAULT OPAQUE DOOR U-FACTORS
DOOR TYPE | OPAQUE U-FACTOR |
Uninsulated Metal | 1.20 |
Insulated Metal | 0.60 |
Wood | 0.50 |
Insulated, nonmetal edge, not exceeding 45% glazing, any glazing double pane | 0.35 |
TABLE 1101.10.3(3)
DEFAULT GLAZED FENESTRATION SHGC AND VT
SINGLE GLAZED | DOUBLE GLAZED | GLAZED BLOCK | |||
Clear | Tinted | Clear | Tinted | ||
SHGC | 0.8 | 0.7 | 0.7 | 0.6 | 0.6 |
VT | 0.6 | 0.3 | 0.6 | 0.3 | 0.6 |
BUILDING THERMAL ENVELOPE
Exceptions:
TABLE 1102.1.2
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
CLIMATE ZONE | FENESTRATION U-FACTORb | SKYLIGHTb U-FACTOR | GLAZED FENESTRATION SHGCb,e | CEILING R-VALUE | WOOD FRAME WALL R-VALUE | MASS WALL R-VALUEi | FLOOR R-VALUE | BASEMENTc WALL R-VALUE | SLABd R-VALUE & DEPTH | CRAWL SPACEc WALL R-VALUE |
4 except Marine | 0.32 | 0.55 | 0.40 | 49 | 20 or 13 + 5h | 8/13 | 19 | 10 /13 | 10, 2 ft | 10/13 |
5 and Marine 4 | 0.30 | 0.55 | NR | 49 | 20 or 13 + 5h | 13/17 | 30g | 10/13 | 10, 2 ft | 10/13 |
For SI: 1 foot = 304.8 mm.
NR = Not Required.
a. R-values are minimums. U-factors and SHGC are maximums. Where insulation is installed in a cavity that is less than the label or design thickness of the insulation, the installed R-value of the insulation shall be not less than the R-value specified in the table.
b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
Exception: Deleted.
c. "10/13" means R-10 continuous insulation on the interior or exterior of the home or R-13 cavity insulation on the interior of the basement wall.
d. R-5 insulation shall be provided under the full slab area of a heated slab in addition to the required slab edge insulation R-value for slabs. as indicated in the table. The slab edge insulation for heated slabs shall not be required to extend below the slab.
e. There are no SHGC requirements in the Marine Zone.
f. Basement wall insulation shall not be required in warm-humid locations as defined by Figure 1101.10 and Table 1101.10.
g. Alternatively, insulation sufficient to fill the framing cavity providing not less than an R-value of R-19.
h. The first value is cavity insulation, the second value is continuous insulation. Therefore, as an example, "13+5" means R-13 cavity insulation plus R-5 continuous insulation.
i. Mass walls shall be in accordance with Section 1102.2.5. The second R-value applies where more than half of the insulation is on the interior of the mass wall.
TABLE 1102.1.4
EQUIVALENT U-FACTORSa
CLIMATE ZONE | FENESTRATION U-FACTOR | SKYLIGHT U-FACTOR | CEILING U-FACTOR | FRAME WALL U-FACTOR | MASS WALL U-FACTORb | FLOOR U-FACTOR | BASEMENT WALL U-FACTOR | CRAWL SPACE WALL U-FACTOR |
4 except Marine | 0.32 | 0.55 | 0.026 | 0.060 | 0.098 | 0.047 | 0.059 | 0.065 |
5 and Marine 4 | 0.30 | 0.55 | 0.026 | 0.060 | 0.082 | 0.033 | 0.059 | 0.065 |
a. Nonfenestration U-factors shall be obtained from measurement, calculation or an approved source.
b. Mass walls shall be in accordance with Section 1102.2.5. Where more than half the insulation is on the interior, the mass wall U-factors shall not exceed 0.087 in Climate Zone 4, and 0.065 in Climate Zone 5.
c. In warm-humid locations as defined by Figure 1101.7 and Table 1101.7, the basement wall U-factor shall not exceed 0.360.
Exception: Vertical doors providing access from conditioned spaces to unconditioned spaces that comply with the fenestration requirements of Table 1102.1.2 based on the applicable climate zone specified in Section 1101.7.
TABLE 1102.2.6
STEEL-FRAME CEILING, WALL AND FLOOR INSULATION R-VALUES
WOOD FRAME R-VALUE REQUIREMENT | COLD-FORMED STEEL-FRAME EQUIVALENT R-VALUEa |
Steel Truss Ceilingsb | |
R-30 | R-38 or R-30 + 3 or R-26 + 5 |
R-38 | R-49 or R-38 + 3 |
R-49 | R-38 + 5 |
Steel Joist Ceilingsb | |
R-30 | R-38 in 2 x 4 or 2 x 6 or 2 x 8 R-49 in any framing |
R-38 | R-49 in 2 x 4 or 2 x 6 or 2 x 8 or 2 x 10 |
Steel-Framed Wall, 16 inches on center | |
R-13 | R-13 + 4.2 or R-21 + 2.8 or R-0 + 9.3 or R-15 + 3.8 or R-21 + 3.1 |
R-13 + 3 | R-0 + 11.2 or R-13 + 6.1 or R-15 + 5.7 or R-19 + 5.0 or R-21 + 4.7 |
R-20 | R-0 + 14.0 or R-13 + 8.9 or R-15 + 8.5 or R-19 + 7.8 or R-19 + 6.2 or R-21 + 7.5 |
R-20 + 5 | R-13 + 12.7 or R-15 + 12.3 or R-19 + 11.6 or R-21 + 11.3 or R-25 + 10.9 |
R-21 | R-0 + 14.6 or R-13 + 9.5 or R-15 + 9.1 or R-19 + 8.4 or R-21 + 8.1 or R-25 + 7.7 |
Steel-Framed Wall, 24 inches on center | |
R-13 | R-0 + 9.3 or R-13 + 3.0 or R-15 + 2.4 |
R-13 + 3 | R-0 + 11.2 or R-13 + 4.9 or R-15 + 4.3 or R-19 + 3.5 or R-21 + 3.1 |
R-20 | R-0 + 14.0 or R-13 + 7.7 or R-15 + 7.1 or R-19 + 6.3 or R-21 + 5.9 |
R-20 + 5 | R-13 + 11.5 or R-15 + 10.9 or R-19 + 10.1 or R-21 + 9.7 or R-25 + 9.1 |
R-21 | R-0 + 14.6 or R-13 + 8.3 or R-15 + 7.7 or R-19 + 6.9 or R-21 + 6.5 or R-25 + 5.9 |
Steel Joist Floor | |
R-13 | R-19 in 2 x 6, or R-19 + 6 in 2 x 8 or 2 x 10 |
R-19 | R-19 + 6 in 2 x 6, or R-19 + 12 in 2 x 8 or 2 x 10 |
a. The first value is cavity insulation R-value, the second value is continuous insulation R-value. Therefore, for example, "R-30+3" means R-30 cavity insulation plus R-3 continuous insulation.
b. Insulation exceeding the height of the framing shall cover the framing.
Exception: As an alternative, the floor framing-cavity insulation shall be in contact with the topside of sheathing or continuous insulation installed on the bottom side of floor framing where combined with insulation that meets or exceeds the minimum wood frame wall R-value in Table 1102.1.2 and that extends from the bottom to the top of all perimeter floor framing members.
Exception: For sunrooms with thermal isolation, and enclosing conditioned space, the following exceptions to the insulation requirements of this code shall apply:
Dynamic glazing shall be permitted to satisfy the SHGC requirements of Table 1102.1.2 provided that the ratio of the higher to lower labeled SHGC is greater than or equal to 2.4, and the dynamic glazing is automatically controlled to modulate the amount of solar gain into the space in multiple steps. Dynamic glazing shall be considered separately from other fenestration, and area-weighted averaging with other fenestration that is not dynamic glazing shall be prohibited.
Exception: Dynamic glazing shall not be required to comply with this section where both the lower and higher labeled SHGC comply with the requirements of Table 1102.1.2.
Exception: In Climate Zones 2 through 8, for sunrooms with thermal isolation and enclosing conditioned space, the fenestration U-factor shall not exceed 0.45 and the skylight U-factor shall not exceed 0.70.
During testing:
Exception: Existing buildings complying with Section 1107.
Exception: Site-built fenestration products.
TABLE 1102.4.1.1
AIR BARRIER AND INSULATION INSTALLATIONa
COMPONENT | AIR BARRIER CRITERIA | INSULATION INSTALLATION CRITERIA |
General requirements | A continuous air barrier shall be installed in the building envelope. The exterior thermal envelope contains a continuous air barrier. Breaks or joints in the air barrier shall be sealed. | Air-permeable insulation shall not be used as a sealing material. |
Ceiling/attic | The air barrier in any dropped ceiling or soffit shall be aligned with the insulation and any gaps in the air barrier sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. | The insulation in any dropped ceiling/soffit shall be aligned with the air barrier. |
Walls | The junction of the foundation and sill plate shall be sealed. The junction of the top plate and the top of exterior walls shall be sealed. Knee walls shall be sealed. | Cavities within corners and headers of frame walls shall be insulated by completely filling the cavity with a material having a thermal resistance of not less than R-3 per inch. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and in continuous alignment with the air barrier. |
Windows, skylights and doors | The space between framing and skylights, and the jambs of windows and doors, shall be sealed. | - |
Rim joists | Rim joists shall include the air barrier. | Rim joists shall be insulated. |
Floors including cantilevered floors and floors above garages. | The air barrier shall be installed at any exposed edge of insulation. | Floor framing cavity insulation shall be installed to maintain permanent contact with the underside of subfloor decking. Alternatively, floor framing cavity insulation shall be in contact with the top side of sheathing or continuous insulation installed on the underside of floor framing; and extending from the bottom to the top of all perimeter floor framing members. |
Crawl space walls | Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. | Crawl space insulation, where provided instead of floor insulation, shall be permanently attached to the walls. |
Shafts, penetrations | Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. | - |
Narrow cavities | - | Batts to be installed in narrow cavities shall be cut to fit or narrow cavities shall be filled with insulation that on installation readily conforms to the available cavity space Narrow cavities less than 1/2" may be left void. |
Garage separation | Air sealing shall be provided between the garage and conditioned spaces. | - |
Recessed lighting | Recessed light fixtures installed in the building thermal envelope shall be sealed to the finished surface. | Recessed light fixtures installed in the building thermal envelope shall be air tight and IC rated. |
Plumbing and wiring | - | In exterior walls, batt insulation shall be cut neatly to fit around wiring and plumbing or insulation that on installation, readily conforms to available space, shall extend behind piping and wiring. |
Shower/tub on exterior wall | The air barrier installed at exterior walls adjacent to showers and tubs shall separate the wall from the shower or tub. | Exterior walls adjacent to showers and tubs shall be insulated. |
Electrical/phone box on exterior walls | The air barrier shall be installed behind electrical and communication boxes. Alternatively, air-sealed boxes shall be installed. | - |
HVAC register boots | HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the subfloor, wall covering or ceiling penetrated by the boot. | - |
Concealed sprinklers | Where required to be sealed, concealed fire sprinklers shall only be sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ceilings. | - |
a. Inspection of log walls shall be in accordance with the provisions of ICC 400.
Exceptions:
SYSTEMS
Exception: Ducts located completely inside conditioned space.
Exceptions:
A written report of the results of the test shall be signed by the party conducting the test and provided to the building official.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole-house mechanical ventilation, the air handler shall be powered by an electronically commutated motor.
TABLE 1103.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACYa
FAN LOCATION | AIR FLOW RATE MINIMUM (CFM) | MINIMUM EFFICACY (CFM/WATT) | AIR FLOW RATE MAXIMUM (CFM) |
HRV or ERV | Any | 1.2 cfm/watt | Any |
Range hoods | Any | 2.8 cfm/watt | Any |
In-line fan | Any | 2.8 cfm/watt | Any |
Bathroom, utility room | 10 | 1.4 cfm/watt | < 90 |
Bathroom, utility room | 90 | 2.8 cfm/watt | Any |
For SI: 1 cubic foot per minute = 28.3 L/min.
a. When tested in accordance with HVI Standard 916.
ELECTRICAL POWER AND LIGHTING SYSTEMS (MANDATORY)
SIMULATED PERFORMANCE ALTERNATIVE (PERFORMANCE)
Exception: The energy use based on source energy expressed in Btu (J) or Btu per square foot (J/m2) of conditioned floor area shall be permitted to be substituted for the energy cost. The source energy multiplier for electricity shall be 3.16. The source energy multiplier for fuels other than electricity shall be 1.1.
Compliance reports shall include information in accordance with Sections 1105.4.2.1 and 1105.4.2.2. Where the proposed design of a building could be built on different sites where the cardinal orientation of the building on each site is different, compliance of the proposed design for the purposes of the application for the building permit shall be based on the worst-case orientation, worst-case configuration, worst-case building air leakage and worst-case duct leakage. Such worst-case parameters shall be used as inputs to the compliance software for energy analysis.
TABLE 1105.5.2(1)
SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS
For SI: 1 square foot = 0.93m2, 1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (US) = 3.785 L, °C = (°F-32)/ 1.8, 1 degree = 0.79 rad.
a. The measured air exchange rate shall be determined by testing conducted in accordance with RESNET/ICC 380, ASTM E779 or ASTM E1827. Hourly calculations as specified in the ASHRAE Handbook of Fundamentals, or the equivalent, shall be used to detemine the energy loads resulting from infiltration.
b. The combined air exchange rate for infiltration and mechanical ventilation shall be determined in accordance with Equation 43 of 2001 ASHRAE Handbook of Fundamentals, page 26.24 and the "Whole-house Ventilation" provisions of 2001 ASHRAE Handbook of Fundamentals, page 26.19 for intermittent mechanical ventilation.
c. Thermal storage element shall mean a component that is not part of the floors, walls or ceilings that is part of a passive solar system, and that provides thermal storage such as enclosed water columns, rock beds, or phase-change containers. A thermal storage element shall be in the same room as fenestration that faces within 15 degrees ( 0.26 rad) of true south, or shall be connected to such a room with pipes or ducts that allow the element to be actively charged.
d. For a proposed design with multiple heating, cooling or water heating systems using different fuel types, the applicable standard reference design system capacities and fuel types shall be weighted in accordance with their respective loads as calculated by accepted engineering practice for each equipment and fuel type present.
e. For a proposed design without a proposed heating system, a heating system having the prevailing federal minimum efficiency shall be assumed for both the standard reference design and proposed design.
f. For a proposed design home without a proposed cooling system, an electric air conditioner having the prevailing federal minimum efficiency shall be assumed for both the standard reference design and the proposed design.
g. For a proposed design with a nonstorage-type water heater, a 40-gallon storage-type water heater having the prevailing federal minimum energy factor for the same fuel as the predominant heating fuel type shall be assumed. For a proposed design without a proposed water heater, a 40-gallon storage-type water heater with the prevailing federal minimum efficiency for the same fuel as the predominant heating fuel type shall be assumed for both the proposed design and standard reference design.
h. For residences with conditioned basements, R-2 and R-4 residences, and for townhouses, the following formula shall be used to detemine glazing area:
AF = AsXFAxF
where:
AF= Total glazing area.
As= Standard reference design total glazing area.
FA= Above-grade thermal boundary gross wall area)/(above-grade boundary wall area + 0.5 × below-grade boundary wall area).
F= (above-grade thermal boundary wall area)/(above-grade thermal boundary wall area + common wall area) or 0.56, whichever is greater.
and where:
Thermal boundary wall is any wall that separates conditioned space from unconditioned space or ambient conditions.
Above-grade thermal boundary wall is any thermal boundary wall component not in contact with soil.
Below-grade boundary wall is any thermal boundary wall in soil contact.
Common wall area is the area of walls shared with an adjoining dwelling unit. L and CFA are in the same units.
TABLE 1105.5.2(2)
DEFAULT DISTRIBUTION SYSTEM EFFICIENCIES FOR PROPOSED DESIGNSa
DISTRIBUTION SYSTEM CONFIGURATION AND CONDITION | FORCED AIR SYSTEMS | HYDRONIC SYSTEMSb |
Distribution system components located in unconditioned space | - | 0.95 |
Untested distribution systems entirely located in conditioned spacec | 0.88 | 1 |
"Ductless" systemsd | 1 | - |
For SI: 1 cubic foot per minute = 0.47 L/s, 1 square foot = 0.093 m2, 1 pound per square inch = 6895 Pa, 1 inch water gauge = 1250 Pa.
a. Default values this table are for untested distribution systems, which must still meet minimum requirements for duct system insulation.
b. Hydronic systems shall mean those systems that distribute heating and cooling energy directly to individual spaces using liquids pumped through closed-loop piping and that do not depend on ducted, forced airflow to maintain space temperatures.
c. Entire system in conditioned space shall mean that no component of the distribution system, including the air handler unit, is located outside of the conditioned space.
d. Ductless systems shall be allowed to have forced airflow across a coil but shall not have any ducted airflow external to the manufacturer's air handler enclosure.
ENERGY RATING INDEX COMPLIANCE ALTERNATIVE
Exception: Supply and return ducts not completely inside the building thermal envelope shall be insulated to an R-value of not less than R-6.
(Equation 11-1)
Energy used to recharge or refuel a vehicle used for transportation on roads that are not on the building site shall not be included in the ERI reference design or the rated design.
TABLE 1106.4
MAXIMUM ENERGY RATING INDEX
CLIMATE ZONE | ENERGY RATING INDEXa |
4 | 62 |
5 | 61 |
a. Where on-site renewable energy is included for compliance using the ERI analysis of Section 1106.4, the building shall meet the mandatory requirements of Section 1106.2, and the building thermal envelope shall be greater than or equal to the levels of efficiency and SHGC in Table 1102.1.2 or Table 1102.1.4.
Exception: Where an otherwise identical building model is offered in multiple orientations, compliance for any orientation shall be permitted by documenting that the building meets the performance requirements in each of the four (north, east, south and west) cardinal orientations.
EXISTING BUILDINGS-GENERAL
TABLE 1107.4.1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
CLIMATE ZONE | FENESTRATION U-FACTORb | SKYLIGHTb U-FACTOR | GLAZED FENESTRATION SHGCb | CEILING R-VALUE | WOOD FRAME WALL R-VALUE | MASS WALLR-VALUEi | FLOOR R-VALUE | BASEMENT cWALL R-VALUE | SLABd R-VALUE AND DEPTH | CRAWL SPACEcWALL R-VALUE |
4 | 0.35 | 0.60 | NR | 38 | 13 | 5/10 | 19 | 10/13 | 10, 2 ft | 10/13 |
5 | 0.35 | 0.60 | NR | 38 | 20 or 13 + 5h | 13/17 | 30g | 10/13 | 10, 2 ft | 10/13 |
a.R-values are minimums. U-factors and solar heat gain coefficient (SHGC)are maximums. R-19 batts compressed in to nominal 2 x 6 framing cavity such that the R-value is reduced by R-1 or more shall be marked with the compressed batt R-value in addition to the full thickness R-value.
b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
c. "10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.
d. R-5 shall be added to the required slab edge R-values for heated slabs.
e. Deleted.
f. Deleted.
g. Or insulation sufficient to fill the framing cavity, R-19 minimum.
h. "13+5" means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathingcovers 25% or less of the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25% of exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2.
i. The second R-value applies when more than half the insulation is on the interior of the mass wall.
j. Deleted.
ADDITIONS
Exceptions:
Exception: Where ducts from an existing heating and cooling system are extended to an addition, duct systems with less than 40 linear feet ( 12.19 m) in unconditioned spaces shall not be required to be tested in accordance with Section 1103.3.3
ALTERATIONS
Alterations to an existing building, building system or portion thereof shall conform to the provisions of this chapter as they relate to new construction without requiring the unaltered portions of the existing building or building system to comply with this chapter. Alterations shall not create an unsafe or hazardous condition or overload existing building systems. Alterations shall be such that the existing building or structure does not use more energy than the existing building or structure prior to the alteration. Alterations to existing buildings shall comply with Sections 1109.1.1 through 1109.2.
Exception: The following alterations shall not be required to comply with the requirements for new construction provided that the energy use of the building is not increased:
Exception: Where ducts from an existing heating and cooling system are extended, duct systems with less than 40 linear feet ( 12.19 m) in unconditioned spaces shall not be required to be tested in accordance with Section 1103.3.3.
Exception: Alterations that replace less than 50 percent of the luminaires in a space, provided that such alterations do not increase the installed interior lighting power.
Exception: Where the simulated performance option in Section 1105 is used to comply with this section, the annual energy cost of the proposed design is permitted to be 110 percent of the annual energy cost otherwise allowed by Section 1105.3.
REPAIRS
CHANGE OF OCCUPANCY OR USE
Exception: Where the simulated performance option in Section 1105 is used to comply with this section, the annual energy cost of the proposed design is permitted to be 110 percent of the annual energy cost allowed by Section 1105.3.
OHIO HOME BUILDERS ASSOCIATION (OHBA) ALTERNATIVE ENERGY CODE OPTION
Exception: Portions of the building envelope that do not enclose conditioned space are exempt from thermal envelope provisions of this section.
TABLE 1112.1.5(1)
DEFAULT GLAZED FENESTRATION U-FACTORS
FRAME TYPE | SINGLE PANE | DOUBLE PANE | SKYLIGHT | |
Single | Double | |||
Metal | 1.2 | 0.8 | 2 | 1.3 |
Metal with thermal break | 1.1 | 0.65 | 1.9 | 1.1 |
Nonmetal or metal clad | 0.95 | 0.55 | 1.75 | 1.05 |
Glazed block | 0.6 |
TABLE 1112.1.5(2)
DEFAULT DOOR U-FACTORS
DOOR TYPE | U-FACTOR |
Uninsulated metal | 1.2 |
Insulated metal | 0.6 |
Wood | 0.5 |
Insulated, nonmetal edge, max 45% glazing, any glazing double pane | 0.35 |
TABLE 1112.1.5(3)
DEFAULT GLAZED FENESTRATION SHGC
SINGLE GLAZED | DOUBLE GLAZED | GLAZED BLOCK | ||
Clear | Tinted | Clear | Tinted | |
0.8 | 0.7 | 0.7 | 0.6 | 0.6 |
TABLE 1112.2.1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
FENESTRATION U-FACTORb | SKYLIGHTb U-FACTOR | GLAZED FENESTRATION SHGCb,e | CEILING R-VALUE | WOOD FRAME WALL R-VALUE | MASS WALL R-VALUEi | FLOOR R-VALUE | BASEMENTc WALL R-VALUE | SLABd R-VALUE AND DEPTH | CRAWL SPACEc WALL R-VALUE | |
Compliance Path #1 | 0.32 | 0.60 | NR | 49 | 15 or 13 + 3h | 13/17 | 30g | 10/13 (minimum 4 feet) | 10, 2 ft | 10/13 |
Compliance Path #2 | 0.32 | 0.60 | NR | 49 | 13 | 13/17 | 30g | 10/13 (minimum 4 feet) | 10, 2 ft | 10/13 |
a. R-values are minimums. U-factors and solar heat gain coefficient (SHGC) are maximums. R-19 batts compressed in to nominal 2 x 6 framing cavity such that the R-value is reduced by R-1 or more shall be marked with the compressed batt R-value in addition to the full thickness R-value.
b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
c. "10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.
d. R-5 shall be added to the required slab edge R-values for heated slabs.
e. Deleted.
f. Deleted.
g. Or insulation sufficient to fill the framing cavity, R-19 minimum.
h. "13+3" means R-13 cavity insulation plus R-3 insulated sheathing. If structural sheathing covers 25% or less of the exterior, insulating sheathing is not required where structural sheathing is used.
i. The second R-value applies when more than half the insulation is on the interior of the mass wall.
j. Deleted.
TABLE 1112.2.1.2
EQUIVALENT U-FACTORSa
FENESTRATION U-FACTOR | SKYLIGHT U-FACTOR | CEILING U-FACTOR | FRAME WALL U-FACTOR | MASS WALL U-FACTORb | FLOOR U-FACTOR | BASEMENT WALL U-FACTOR | CRAWL SPACE WALL U-FACTOR | |
Compliance Path #1 | 0.32 | 0.60 | 0.026 | 0.077 | 0.082 | 0.033 | 0.059 (minimum 4 feet) | 0.065 |
Compliance Path #2 | 0.32 | 0.60 | 0.026 | 0.082 | 0.082 | 0.033 | 0.059 (minimum 4 feet) | 0.065 |
a.Nonfenestration U-factors shall be obtained from measurement, calculation or approved referenced publications approved in accordance with this code.
b.When more than half the insulation is on the interior, the mass wall U-factors shall be the same as the frame wall U-factor.
TABLE 1112.2.2.5
STEEL-FRAME CEILING, WALL AND FLOOR INSULATION (R-VALUE)
WOOD FRAME R-VALUE REQUIREMENT | COLD-FORMED STEEL EQUIVALENT R-VALUEa |
Steel Truss Ceilingsa | |
R-30 | R-38 or R-30 + 3 or R-26 + 5 |
R-38 | R-49 or R-38 + 3 |
R-49 | R-38 + 5 |
Steel Joist Ceilingsb | |
R-30 | R-38 in 2 x 4 or 2 x 6 or 2 x 8 R-49 in any framing |
R-38 | R-49 in 2 x 4 or 2 x 6 or 2 x 8 or 2 x 10 |
Steel Framed Wall | |
R-13 | R-13 + 5 or R15 + 4 or R-21 + 3 or R-0 + 10 |
R-15 or R-13+3 | R-0 + 11.2 or R-13 + 6.1 or R-15 + 5.7 or R-19 + 5.0 or R-21 + 4.7 |
R-19 | R-13 + 9 or R-19 + 8 or R-25 + 7 |
R-21 | R-13 + 10 or R-19 + 9 or R-25 + 8 |
Steel Joist Floor | |
R-13 | R-19 in 2 x 6, R-19 + 6 in 2 x 8 or 2 x 10 |
R-19 | R-19 + 6 in 2 x 6, R-19 + 12 in 2 x 8 or 2 x 10 |
R-30 | R-19 + 6 in 2 x 6, R-19 + 12 in 2 x 8 or 2 x 10 |
For SI: 1 inch = 25.4 mm.
a.Cavity insulation R-value is listed first, followed by continuous insulation R-value.
b.Insulation exceeding the height of the framing shall cover the framing.
Attic access openings.
Rim joists junction.
During testing:
Exception: Site-built fenestration products.
Exception: Ducts or portions thereof located completely inside the building thermal envelope.
TABLE 1112.3.2.2(a)
POST-CONSTRUCTION DUCT TIGHTNESS TESTING
Leakage to Outdoors (per 100 ft2(9.29 m2) of conditioned floor area) | Total Leakage (per 100 ft2(9.29 m2) of conditioned floor area) | |
Compliance Path #1 | <= 6 cfm ( 2.83 L/s) | <= 9 cfm ( 4.24 L/s) |
Compliance Path #2 | <= 4 cfm ( 1.89 L/s) | <= 6 cfm ( 2.83 L/s) |
TABLE 1112.3.2.2(b)
ROUGH-IN DUCT TIGHTNESS TESTING
Total Leakage - with air handler installed (per 100 ft2(9.29 m2) of conditioned floor area) | Total Leakage - without air handler installed (per 100 ft2(9.29 m2) of conditioned floor area) | |
Compliance Path #1 | <= 6 cfm ( 2.83 L/s) | <= 4 cfm ( 1.89 L/s) |
Compliance Path #2 | <= 4 cfm ( 1.89 L/s) | <= 3 cfm (1.41 L/s) |
Exception: Duct tightness test is not required if the air handler and all ducts are located within conditioned space.
Replaces: 4101:8-11-01
Ohio Admin. Code 4101:8-11-01
Five Year Review (FYR) Dates: 07/01/2024
Promulgated Under: 119.03
Statutory Authority: 3781.10(A)(1)
Rule Amplifies: 3781.01, 4740.14, 3791.04, 3781.11, 3781.10, 3781.06
Prior Effective Dates: 01/01/2008, 01/01/2009, 01/01/2013, 07/01/2014