(F) For single property community water systems and noncommunity water systems, other backflow preventers for plumbing applications may be accepted by the director to abate or control the cross connection, if the water use practice is not specifically addressed in this chapter, and the backflow preventer is identified as an approved isolation backflow prevention device in accordance with section 608 of rule 4101:3-6-01 of the Administrative Code adopted by the board of building standards for the corresponding water use practice. The consumer shall ensure these backflow preventers are inspected at least once every twelve months, maintained in proper working order, tested, if applicable, and maintain records of the results thereof. This paragraph does not apply to water use practices posing a severe health hazard or in cases where an auxiliary water system is on or available to the premises. [Comment: For dates of non-regulatory government publications, publications of recognized organizations and associations, test methods, federal rules, and federal statutory provisions referenced in this rule, see paragraph (AA) of rule 3745-95-01 of the Administrative Code titled "Referenced materials."]
Replaces: 3745-95-06