Valves shall be installed so that they are accessible from the surface of the ground by means of an open stack.
Table 1: Water service pipe (outside use)
MATERIAL | STANDARD |
Copper or copper alloy pipe | ASTM B42-2015a; ASTM B302-2017 |
Copper or Copper alloy tubing (Type K, WK, L, WI, M or WM) | ASTM B75/B75M-2011; ASTM B88-2016; ASTM B251-2017; ASTM B447-2012a |
Chlorinated polyvinyl chloride (CPVC) | ASTM D2846/D2846M-2017be1; ASTM F441/F441M-2015; ASTM F442/ F442M-2013e1; CSA B 137.6 2017 |
Ductile iron water pipe | AWWA C151 2009; AWWA C115 2011 |
Polybutylene (PB) plastic pipe and tubing | CSA B 137.8 2017 |
Polyethylene (PE) plastic pipe | ASTM D2239-2012a; CSA B 137.1 2017 |
Polyethylene (PE) plastic tubing | ASTM D2737-2012a; CSA B 137.1 2017 |
Cross-linked polyethylene (PEX) plastic tubing | ASTM F876-2017; ASTM F877-2018; CSA B 137.5 2017 |
Polyvinyl chloride (PVC) plastic pipe | ASTM D1785-2015e1; ASTM D2241-2015; ASTM D2672-2014; CSA B 137.3 2017 |
Stainless-steel | ASTM A269/A269M-2015a; ASTM A312 / A312M-2017 |
Table 2: Water distribution pipe (inside use)
MATERIAL | STANDARD |
Brass pipe | ASTM B43-2015 |
Chlorinated polyvinyl chloride (CPVC) | ASTM D2846/D2846M-2017be1; ASTM F441/F441M-2015; ASTM F442/ F442M-2013e1; CSA B 137.6 2017 |
Copper or copper alloy pipe | ASTM B42-2015a; ASTM B302-2017 |
Copper or Copper alloy tubing (Type K, WK, L, WI, M or WM) | ASTM B75/B75M-2011; ASTM B88-2016; ASTM B251-2017; ASTM B447-2012a |
Cross-linked polyethylene (PEX) plastic tubing | ASTM F877-2018; CSA B 137.5 2017 |
Polybutylene (PB) plastic pipe and tubing | CSA B 137.8 2017 |
Polyvinyl chloride (PVC) plastic pipe | ASTM D1785-2015e1; ASTM D2241-2015; ASTM D2672-2014; CSA B 137.3 2017 |
Stainless-steel | ASTM A269/A269M-2015a; ASTM A312/ A312M-2017 |
Replaces: 3701-28-08
Ohio Admin. Code 3701-28-08
Five Year Review (FYR) Dates: 09/20/2024
Promulgated Under: 119.03
Statutory Authority: 3701.344
Rule Amplifies: 3701.344
Prior Effective Dates: 01/01/1981, 01/01/2000, 04/01/2011