Exceptions:
"Dutch door."
"Existing."
The provisions of this rule shall not be construed to allow the elimination of fire protection systems or a reduction in the level of fire safety provided in buildings constructed in accordance with previously adopted codes.
Exception: Group U occupancies.
Table 1103.1
Occupancy and use requirementsa
Section | Use | Occupancy classification | ||||||||||||||||||||
High rise | Atrium or covered mall | Underground building | A | B | E | F | H-1 | H-2 | H-3 | H-4 | H-5 | I-1 | I-2 | I-3 | I-4 | M | R-1 | R-2 | R-3 | R-4 | S | |
1103.2 | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R |
1103.3 | R | -- | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R |
1103.4.1 | R | -- | R | - | - | - | - | - | - | - | - | - | - | R | R | - | - | - | - | - | - | - |
1103.4.2 | R | -- | R | R | R | R | R | R | R | R | R | R | R | - | - | R | R | R | R | - | R | R |
1103.4.3 | R | -- | R | R | R | R | R | R | R | R | R | R | R | - | - | R | R | R | R | - | R | R |
1103.4.4 | -- | R | -- | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
1103.4.5 | -- | -- | -- | - | R | - | - | - | - | - | - | - | - | - | - | - | R | - | - | - | - | - |
1103.4.6 | -- | -- | -- | R | - | R | R | R | R | R | R | R | R | R | R | R | - | R | R | R | R | R |
1103.4.7 | -- | -- | -- | R | - | R | R | R | R | R | R | R | R | R | R | R | - | R | R | R | R | R |
1103.4.8 | R | ---- | R | R | R | R | R | R | R | R | R | R | R | -- | -- | R | R | R | R | R | R | R |
1103.4.9 | R | ---- | ---- | -- | - | - | - | -- | -- | -- | -- | -- | -- | R | -- | -- | - | -- | -- | -- | -- | - |
1103.5.1 1103.5.2b | -- | -- | -- | - | - | - | - | - | - | - | - | - | - | R | - | - | - | - | - | - | - | - |
1103.5.3 | --- | --- | --- | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R |
1103.6.1 | R | -- | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | - | R | R |
1103.6.2 | R | -- | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | - | R | R |
1103.7.1 | -- | -- | -- | - | - | R | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
1103.7.2 | -- | -- | -- | - | - | - | - | - | - | - | - | - | R | - | - | - | - | - | - | - | - | - |
1103.7.3 | -- | -- | -- | - | - | - | - | - | - | - | - | - | - | R | - | - | - | - | - | - | - | - |
1103.7.4 | -- | -- | -- | - | - | - | - | - | - | - | - | - | - | - | R | - | - | - | - | - | - | - |
1103.7.5 | -- | -- | -- | - | - | ..- | - | - | - | - | - | - | - | - | - | - | - | R | - | - | - | - |
1103.7.6 | -- | -- | -- | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | R | - | - | - |
1103.7.7 | -- | -- | -- | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | R | - |
1103.8 | -- | -- | -- | - | - | - | - | - | - | - | - | - | R | - | - | - | - | R | R | R | R | - |
1103.9 | R | -- | -- | - | - | - | - | - | - | - | - | - | R | R | - | R | - | R | R | R | R | - |
1104 | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R | R |
1105 | -- | -- | -- | -- | - | - | - | -- | -- | -- | -- | -- | -- | R | -- | -- | - | -- | -- | -- | -- | - |
1106 | -- | -- | -- | -- | - | - | - | -- | -- | - | -- | -- | -- | R | -- | -- | - | -- | -- | -- | -- | - |
R=The building is required to comply.
Exception: Where it is determined by the fire code official that the radio coverage system is not needed.
Exceptions:
Elimination of previously installed Phase I emergency recall or Phase II emergency in-car systems shall not be permitted.
Exceptions:
Exceptions:
Exceptions:
Exceptions:
Exception: Occupancies with an existing, previously approved fire alarm system.
Exceptions:
Exception: Where each sleeping room has a means of egress door opening directly to an exterior egress balcony that leads directly to the exits in accordance with paragraph (U)(1021) of rule 1301:7-7-10 of the Administrative Code, and the building is not more than three stories in height.
Exceptions:
Exception: An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit.
Exception: Buildings less than two stories in height where all sleeping units, attics and crawl spaces are separated by 1-hour fire-resistance-rated construction and each sleeping unit has direct access to a public way, egress court or yard.
Exception: Buildings equipped with single-station smoke alarms meeting or exceeding the requirements of paragraph (G)(2)(k)(i)(907.2.11.1) of rule 1301:7-7-09 of the Administrative Code and where the fire alarm system includes not less than one manual fire alarm box per floor arranged to initiate the alarm.
Exceptions:
Exceptions:
Exceptions:
Exceptions:
Exceptions:
Exceptions:
Exception: Approved self-luminous signs that provide evenly illuminated letters shall have a minimum luminance of 0.06 foot-lamberts ( 0.21 cd/m2).
Exception: Approved signs that provide continuous illumination independent of external power sources are not required to be connected to an emergency electrical system.
Exception: Assembly occupancies used exclusively as a place of worship and having an occupant load of less than 300.
Exception: Buildings used only during daylight hours and that are provided with windows for natural light in accordance with the building code as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Buildings less than 3,000 square feet (279 m2) in gross sales area on one story only, excluding mezzanines.
Exception: Where each sleeping unit has direct access to the outside of the building at grade.
Exception: Where each dwelling unit or sleeping unit has direct access to the outside of the building at grade.
Exception: Where each sleeping unit has direct access to the outside of the building at ground level.
Exceptions:
Exceptions:
Exceptions:
Exceptions:
Table 1104.9
Revolving door speeds
Inside diameter (feet-inches) | Power-driven-type speed control (RPM) | Manual-type speed control (RPM) |
6'6" | 11 | 12 |
7'0" | 10 | 11 |
7'6" | 9 | 11 |
8'0" | 9 | 10 |
8'6" | 8 | 9 |
9'0" | 8 | 9 |
9'6" | 7 | 8 |
10'0" | 7 | 8 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Exception: Other stairways approved by the fire code official.
Exception: Aisle stairs provided with a center handrail are not required to have additional handrails.
Exception: In buildings equipped throughout with an approved automatic sprinkler system, opening protection is not required.
Exception: For fire escape stairways serving 10 or fewer occupants, an approved fire escape ladder is allowed to serve as the termination.
Exceptions:
Exceptions:
Exception: A dead-end passageway or corridor shall not be limited in length where the length of the dead-end passageway or corridor is less than 2.5 times the least width of the dead-end passageway or corridor.
Table 1104.18
Common path, dead-end and travel distance limits (by occupancy)
Occupancy | Common path limit | Dead-end limit | Travel distance limit | |||
Unsprinklered (feet) | Sprinklered (feet) | Unsprinklered (feet) | Sprinklered (feet) | Unsprinklered (feet) | Sprinklered (feet) | |
Group A | 20/75a | 20/75a | 20b | 20b | 200 | 250 |
Group Bh | 75 | 100 | 50 | 50 | 200 | 300 |
Group E | 75 | 75 | 20 | 50 | 200 | 250 |
Group F-1, S-1d,h | 75 | 100 | 50 | 50 | 200 | 250 |
Group F-2, S-2d,h | 75 | 100 | 50 | 50 | 300 | 400 |
Group H-1 | 25 | 25 | 0 | 0 | 75 | 75 |
Group H-2 | 50 | 100 | 0 | 0 | 75 | 100 |
Group H-3 | 50 | 100 | 20 | 20 | 100 | 150 |
Group H-4 | 75 | 75 | 20 | 20 | 150 | 175 |
Group H-5 | 75 | 75 | 20 | 20 | 150 | 200 |
Group I-1 | 75 | 75 | 20 | 50 | 200 | 250 |
Group I-2 | Notes e,g | Notes e,g | Note f | Note f | 150 | 200c |
Group I-3 | 100 | 100 | NR | NR | 150c | 200c |
Group I-4 (Day care centers) | NR | NR | 20 | 20 | 200 | 250 |
Group M (Covered or open mall) | 75 | 100 | 50 | 50 | 200 | 400 |
Group M (Mercantile) | 75 | 100 | 50 | 50 | 200 | 400 |
Group R-1 (Hotels) | 75 | 75 | 50 | 50 | 200 | 250 |
Group R-2 (Apartments) | 75 | 125 | 50 | 50 | 200 | 250 |
Group R-3 (One- and two-family) | NR | NR | NR | NR | NR | NR |
Group R-4 (Residential care/assisted living) | NR | NR | NR- | NR | NR | NR |
Group Uf | 75 | 100 | 20 | 50 | 300 | 400 |
NR=No requirements.
For SI: 1 foot =304.8 mm, 1 square foot =0.0929 m2.
Exception: Stairways that continue one-half story beyond their levels of exit discharge need not be provided with barriers where the exit discharge is obvious.
Exceptions:
Exception: Thirty-six inches (914 mm) where the aisle serves less than 50 seats.
Exceptions:
Exception: Thirty-six inches (914 mm) where the aisle serves less than 50 seats.
Exception: Thirty inches (760 mm) for catchment areas serving not more than 60 seats.
Exception: Open, unenclosed stairwells in historic buildings designated as historic under a state or local historic preservation program.
Where the provisions of this rule conflict with the construction requirements that applied at the time of construction, the most restrictive provision shall apply.
Table 1105.2
Floor level limitations for Group I-2 Condition 2
Construction type | Automatic sprinkler system | Allowable floor levela | |||
1 | 2 | 3 | 4 or more | ||
IA | Note b | P | P | P | P |
Note c | P | P | P | P | |
IB | Note b | P | P | P | P |
Note c | P | P | P | P | |
IIA | Note b | P | P | P | NP |
Note c | P | NP | NP | NP | |
IIB | Note b | P | P | NP | NP |
Note c | NP | NP | NP | NP | |
IIIA | Note b | P | P | NP | NP |
Note c | P | NP | NP | NP | |
IIIB | Note b | P | NP | NP | NP |
Note c | NP | NP | NP | NP | |
IV | Note b | P | P | NP | NP |
Note c | NP | NP | NP | NP | |
VA | Note b | P | P | NP | NP |
Note c | NP | NP | NP | NP | |
VB | Note b | P | NP | NP | NP |
Note c | NP | NP | NP | NP |
P = Permitted; NP = Not permitted.
Table 1105.3
Incidental uses in existing Group I-2 occupancies
Room or area | Separation and/or protection |
Furnace room where any piece of equipment is over 400,000 Btu per hour input | 1 hour or provide automatic sprinkler system |
Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower | 1 hour or provide automatic sprinkler system |
Refrigerant machinery room | 1 hour or provide automatic sprinkler system |
Hydrogen fuel gas rooms, not classified as Group H | 2 hours |
Incinerator rooms | 2 hours and provide automatic sprinkler system |
Paint shops not classified as Group H | 2 hours; or 1 hour and provide automatic sprinkler system |
Laboratories and vocational shops, not classified as Group H | 1 hour or provide automatic sprinkler system |
Laundry rooms over 100 square feet | 1 hour or provide automatic sprinkler system |
Patient rooms equipped with padded surfaces | 1 hour or provide automatic sprinkler system |
Physical plant maintenance shops | 1 hour or provide automatic sprinkler system |
Waste and linen collection rooms with containers with total volume of 10 cubic feet or greater | 1 hour or provide automatic sprinkler system |
Storage rooms greater than 100 square feet | 1 hour or provide automatic sprinkler system |
Stationary storage battery systems having a liquid electrolyte capacity of more than 50 gallons for flooded lead-acid, nickel cadmium or VRLA, or more than 1,000 pounds for lithium-ion and lithium metal polymer used for facility standby power, emergency power or uninterruptable power supplies | 2 hours |
For SI: 1 square foot = 0.0929 m2, 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L.
Exception: In smoke compartments not containing patient sleeping rooms, pass-through windows or similar openings shall be permitted in accordance with paragraph (E)(4)(d)(iii)(1105.4.4.3) of this rule.
Exception: Doors shall be permitted to have louvers, transfer grills or similar openings at toilet rooms or bathrooms; storage rooms that do not contain storage of flammable or combustible material; and storage rooms that are not required to be separated as incidental uses.
Exception: Corridor doors in buildings equipped throughout with an automatic sprinkler system.
Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with paragraph (I)(909) of rule 1301:7-7-09 of the Administrative Code, approved alternative protection shall be utilized.
Exceptions:
The size of the refuge area shall provide the following:
Areas of spaces permitted to be included in the calculation of the refuge area are corridors, sleeping areas, treatment rooms, lounge or dining areas and other low-hazard areas.
Exceptions:
Exception: Existing wired glass vision panels in doors shall be permitted to remain.
Exception: Approved existing materials and methods of construction.
Exception: Approved existing materials and methods of construction.
Exception: Where existing duct and air transfer openings in smoke barriers exist without smoke dampers, they shall be permitted to remain. Any changes to existing smoke dampers shall be submitted for review and approved in accordance with section 717 of the building code as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Manual fire alarm boxes in patient sleeping areas shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in paragraph (G)(4)(b)(i)(907.4.2.1) of rule 1301:7-7-09 of the Administrative Code are not exceeded.
Replaces: 1301:7-7-11
Ohio Admin. Code 1301:7-7-11
Five Year Review (FYR) Dates: 12/15/2022
Promulgated Under: 119.03
Statutory Authority: 3737.22, 3737.83, 3737.82
Rule Amplifies: 3737.82, 3737.22, 3737.83
Prior Effective Dates: 11/01/2011, 12/15/2017