N.D. Admin. Code 33.1-14-09-02

Current through Supplement No. 394, October, 2024
Section 33.1-14-09-02 - Nonstandard riveted boilers

The maximum allowable working pressure on the shell of a noncode riveted heating boiler must be determined in accordance with section 33.1-14-05-01 except that the maximum allowable working pressure of a steam heating boiler may not exceed fifteen pounds [103 kilopascals] and a hot water boiler may not exceed thirty pounds [206.85 kilopascals] at a temperature not exceeding two hundred fifty degrees Fahrenheit [120 degrees Celsius].

N.D. Admin Code 33.1-14-09-02

Adopted by Administrative Rules Supplement 2020-377, July 2020, effective 7/1/2020.

General Authority: NDCC 23.1-16

Law Implemented: NDCC 23.1-16