N.D. Admin. Code 33.1-14-07-04

Current through Supplement No. 394, October, 2024
Section 33.1-14-07-04 - Safety valves
1. Each miniature boiler must be equipped with an American society of mechanical engineers approved safety valve set at or below the maximum allowable working pressure.
2. The safety valve must be plainly marked by the manufacturer showing name or identifying trademark, nominal diameter, and pressure at which it is set to release.
3. The safety valve relieving capacity of each boiler must be such that it will discharge all the steam that can be generated by the boiler without allowing the pressure to rise more than six percent above the maximum allowable working pressure.
4. In those cases where the boiler is supplied with feedwater directly from a pressure main or system without the use of a mechanical feeding device, the safety valve must be set to release at a pressure not in excess of ninety-four percent of the lowest pressure obtained in the supply main or system feeding the boiler. Return traps may not be considered mechanical feeding devices.

N.D. Admin Code 33.1-14-07-04

Adopted by Administrative Rules Supplement 2020-377, July 2020, effective 7/1/2020.

General Authority: NDCC 23.1-16

Law Implemented: NDCC 23.1-16