N.D. Admin. Code 33-33-09-01

Current through Supplement No. 395, January, 2025
Section 33-33-09-01 - Emergency lighting

Emergency lighting for means of egress shall be provided in all assisted living facilities. Emergency illumination shall be provided for not less than one and one-half hours in the event of failure of normal lighting. Emergency lighting facilities shall be arranged to provide initial illumination that is not less than an average of one footcandle [10 lux]. Where each living unit has a direct exit to the outside of the building at ground level, no emergency lighting shall be required.

N.D. Admin Code 33-33-09-01

Effective April 1, 2012.

General Authority: NDCC 23-09-02

Law Implemented: NDCC 23-09-02