Lodging establishments or assisted living facilities without direct access from sleeping rooms to the outside shall have hallways or exit corridors equipped with listed smoke detection devices. Hallway or exit corridor smoke detection devices shall be wired into an approved fire alarm system so as to sound an alarm when any of the smoke detection devices are activated. Audible signaling appliances shall be located so as to be clearly heard throughout the facility regardless of the maximum noise level under normal conditions of occupancy. In all cases one appliance must be installed at manufacturer's recommendations or for each thirty feet [9.15 meters] of hallway or exit corridor or fraction thereof.
N.D. Admin Code 33-33-05-02
General Authority: NDCC 23-01-03(3), 23-09-02.1
Law Implemented: NDCC 23-09-02.1