10A N.C. Admin. Code 13F.0308

Current through Register Vol. 39, No. 12, December 1, 2024
Section 13F .0308 - FIRE EXTINGUISHERS
(a) At least one five pound or larger (net charge) A-B-C type fire extinguisher is required for each 2,500 square feet of floor area or fraction thereof.
(b) One five pound or larger (net charge) A-B-C or CO/2 type is required in the kitchen and, where applicable, in the maintenance shop.