Current through Register Vol. 39, No. 11, December 2, 2024
Section 11 R07-29 - WATER METER ACCURACY(a) Installation Test. - Every water service meter, whether new or repaired, shall be in good order and shall be correct to within 2% fast or slow before being installed for the use of any customer.(b) Meter Test Flows. - The following test rates are recommended for conducting test: It is recommended that no less than three rates of flow be used.
Meter | Allowable Range Test Flow Gallons per Minute | Recommended Test Rate Flow | Gallons per Minute |
Size | Min. | Max. | Min. | Med. | Max. |
1 1/2 | 5 | 100 | 5 | 25 | 100 |
2 | 8 | 160 | 8 | 40 | 160 |
3 | 16 | 300 | 15* | 100 | 300 |
4 | 28 | 500 | 15* | 250 | 500 |
6 | 48 | 1000 | 20* | 500 | 1000 |
*Note - A meter failing to register 5% of the water passed at those rates marked * should not be installed without correction.
(c) Method of Testing. - All tests to determine the accuracy of registration of any water service meter shall be made with suitable testing instruments.04 N.C. Admin. Code 11 R07-29