Any waste oil that is proposed to be burned must meet the minimum limitations in Table 1 below:
Table 1
Constituent/Property | Limit |
Polychlorinated Biphenyls (PCB) | < 2 ppm (1) |
Total Halogens | [LESS THAN EQUAL TO] 1,000 ppm (1) |
Sulfur | See 6 NYCRR 225-1(2) |
Gross Heat Content | [GREATOR THAN EQUAL TO] 125,000 (Btu/gal) |
Arsenic | < 5 ppm (1) |
Cadmium | < 2 ppm (1) |
Chromium | < 10 ppm (1) |
Lead | < 100 ppm (1) |
N.Y. Comp. Codes R. & Regs. Tit. 6 §§ 225-2.5