Section 219-2.3 - Design requirements(a) Furnace design must provide for:(1) a residence time for combustion gas of at least one second at no less than 1,800° F; or(2) a residence time for combustion gas and a temperature which, in combination, are shown to be equivalent to paragraph (1) of this subdivision.(b) Furnace design must include auxiliary burners capable of meeting the requirements of section 219-2.4(b) of this Subpart.(c) Control equipment for reducing emissions of hydrogen chloride must be designed such that the flue gas temperature at the outlet from the control device does not exceed 300° F unless a demonstration is made that an equivalent collection of condensible heavy metals and toxic organics can be achieved at a higher outlet temperature or through the use of alternate technologies.N.Y. Comp. Codes R. & Regs. Tit. 6 §§ 219-2.3