N.Y. Comp. Codes R. & Regs. tit. 16 § 255.809

Current through Register Vol. 46, No. 45, November 2, 2024
Section 255.809 - Leaks: instrument sensitivity verification

Each instrument utilized for leakage surveys and investigations must be tested against a known sample or in accordance with the manufacturer's recommended instructions as follows:

(a) after any repair or replacement of parts other than normal maintenance;
(b) once every three months for CGI's and solid-state leak detection instruments and yearly for hydrogen flame ionization (HFI) instruments; and
(c) any time it is suspected that the calibration has changed.

N.Y. Comp. Codes R. & Regs. Tit. 16 § 255.809