Minimum pounds of steam per hour per square foot of surface
[Note: The following TABLE/FORM is too wide to be displayed on one screen. You must print it for a meaningful review of its contents. The table has been divided into multiple pieces with each piece containing information to help you assemble a printout of the table. The information for each piece includes: (1) a three line message preceding the tabular data showing by line # and character # the position of the upper left-hand corner of the piece and the position of the piece within the entire table; and (2) a numeric scale following the tabular data displaying the character positions.] ******************************************************************************* ******** This is piece 1. -- It begins at character 1 of table line 1. ******** ******************************************************************************* Boiled heating surface Hand-fired Stoker-fired Oil, gas, or Hand-fired pulverized-fuel-fired Fire-tube 5 7 8 8 boilers Water-tube 6 8 10 8 boilers 1...+...10....+...20....+...30....+...40....+...50....+...60....+...70....+. ******************************************************************************* ******* This is piece 2. -- It begins at character 77 of table line 1. ******** ******************************************************************************* Waterwall surface Stoker-fired Oil, gas, or pulverized-fuel-fired 10 14 12 16 77......+...90....+....0....+...10....
Note: When a boiler is fired only by a gas having a heat value not in excess of 200 Btu per cubic foot, the minimum safety valve relieving capacity may be based on the values given for hand-fired boilers above.
The minimum capacity of the valve or valves shall be governed by the capacity marking on the boiler.
N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 4-5.2