N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 4-12.4

Current through Register Vol. 46, No. 50, December 11, 2024
Section 4-12.4 - Manual-maximum firing rate over three gallons per hour

After the burner is manually lit, the main flame shall be continually supervised while the burner is firing. The electrical circuit to the main fuel valve shall be automatically de-energized within four seconds after flame failure and the de-energized valve shall automatically close within the next five seconds.