Section 7.8.3.116 - ELECTRICAL CORDS AND RECEPTACLES FOR COMMUNITY HOMES
A. Electrical cords and extension cords must be U/L approved.
B. Electrical cords and extension cords must be replaced as soon as they show wear.
C. Under no circumstances may extension cords be used as a general wiring method, or used in a series.
D. Extension cords must be plugged into an electrical receptacle within the room where used and are not connected in one room and extended to another room.
E. Duplex grounded type electrical receptacles (convenience outlets) must be installed in all areas in sufficient quantities for tasks to be performed as needed.
F. The use of multiple sockets (gang plugs) in electrical receptacles is strictly prohibited. Surge protectors are not considered gang plugs under these regulations.
G. The main electrical service line has a readily available disconnect switch. All staff of the facility must know the location of the electrical disconnect switch and how to operate it in case of an emergency.
H. Facilities that care for children less than six years of age must have safety electrical receptacles or provide protective covers.