Section 7.20.12.70 - ELECTRICAL STANDARDSA. All electrical installation and equipment must comply with all current state and local codes.B. Circuit breakers or fused switches that provide electrical disconnection and overcurrent protection must be:(1) enclosed or guarded to provide a dead front assembly;(2) readily accessible for use and maintenance;(3) set apart from traffic lanes;(4) located in a dry, ventilated space, free of corrosive fumes or gases;(5) able to operate properly in all temperature conditions;(6) located on the same floor and in the same facility area as the circuits they serve;(7) marked showing the area each circuit breaker or fused switch services.C. The use of jumpers or devices to bypass circuit breakers or fused switches is prohibited.N.M. Admin. Code § 7.20.12.70