Maximum Leak Detection Rate Per Test Section Volume | ||
Test Section Volume (Gallons) | Semiannual Test - Leak Detection Rate Not to Exceed (Gallons Per Hour) | Annual Test - Leak Detection Rate Not to Exceed (Gallons Per Hour) |
< 50,000 | 1.0 | 0.5 |
>= 50,000 to < 75,000 | 1.5 | 0.75 |
>= 75,000 to < 100,000 | 2.0 | 1.0 |
>= 100,000 | 3.0 | 1.5 |
N.M. Admin. Code § 20.5.114.1408