Current through Register Vol. 35, No. 23, December 10, 2024
Section 20.5.114.1402 - ADDITIONAL REQUIREMENTS FOR HYBRID STORAGE TANK SYSTEMSA. Owners and operators of hybrid storage tank systems shall, no later than one year after the effective date of these regulations, install redundant automatic shut off and manual override equipment on the piping transferring a regulated substance from the AST to the UST in order to prevent overfills.B. Owners and operators of existing hybrid storage tank systems who replace the underground piping on or after the effective date of these regulations shall install double walled piping including but not limited to the underground remote fill piping. Containment sumps shall be installed at both ends of the underground piping. The new underground piping shall be interstitially monitored monthly in accordance with 20.5.108.811 NMAC or 20.5.8.813 NMAC as applicable upon installation.N.M. Admin. Code § 20.5.114.1402
Adopted by New Mexico Register, Volume XXIX, Issue 14, July 24, 2018, eff. 7/24/2018