Section 20.5.109.917 - SECONDARY CONTAINMENT FOR AST DISPENSERSOwners and operators shall install a containment sump underneath each dispenser system associated with an AST, unless the dispenser is located within secondary containment.
A. Owners and operators shall hydrostatically test the sump upon installation, in accordance with manufacturer's recommendations.B. The following may be used to comply with this containment sump requirement: dispenser liners, under-dispenser containment, dispenser pans, and dispenser sump liners.C. Under-dispenser containment sumps shall be either listed in accordance with an industry standard or code of practice developed by a nationally recognized association or independent testing laboratory for use with flammable and combustible liquids or approved prior to installation by the department in accordance with the alternate methods requirements in 20.5.109.920 NMAC.N.M. Admin. Code § 20.5.109.917