Type of System | Minimum Storage | |
Percentage of Average | ||
Daily Demand | ||
i. | Single, prime source, no interconnection(s), no | 100 percent |
auxiliary power at water source | ||
ii. | Single, prime source, no interconnection(s), | 80 percent |
auxiliary power provided at water source + | ||
iii. | Single, prime source with interconnection(s) ++ | 50 percent |
iv. | Multiple source, no interconnection(s), no | 80 percent |
auxiliary power at water source | ||
v. | Multiple sources, no interconnection(s), | 50 percent |
auxiliary power provided at water source + | ||
vi. | Multiple sources, with interconnection(s) | 50 percent |
vii. | Multiple sources, interconnection(s)++, auxiliary | 30 percent |
power provided at water source + | ||
viii. | Same as vii. above, and distributing more than an | 20 percent |
average of 50 million gallons per day | ||
+ Auxiliary power must be able to supply at least 50 percent of average | ||
production. | ||
++ Combined interconnection(s) must be able to supply at least 50 percent of | ||
average production; contract commitment from supplier is required. |
N.J. Admin. Code § 7:19-6.7