Section 7:14B-6.6 - Methods of release detection for piping(a) Each method of release detection for piping used to meet the requirements of 7:14B-6.2 and 6.3 shall be conducted in accordance with the following:1. Automatic line leak detectors which alert the operator to the presence of a leak by restricting or shutting off the flow of regulated substances through piping or triggering an audible or visual alarm may be used only if they detect leaks of three gallons per hour at 10 pounds per square inch line pressure within one hour. An annual test of the operation of the leak detector shall be conducted in accordance with the manufacturer's requirements;2. A periodic test of piping may be conducted only if it can detect a 0.1 gallon per hour leak rate at one and one-half times the operating pressure; and3. Any of the methods in 7:14B-6.5(a)5 through 8 may be used if they are designed to detect a release from any portion of the underground piping that routinely contains regulated substances.N.J. Admin. Code § 7:14B-6.6