N.J. Admin. Code § 7:14B-4.1A

Current through Register Vol. 56, No. 21, November 4, 2024
Section 7:14B-4.1A - Performance standards for dispenser systems
(a) Each UST system shall be equipped with under-dispenser containment (UDC) for any new dispenser system installed on or after April 11, 2016.
1. A dispenser system is considered new when both the dispenser and the equipment needed to connect the dispenser to the underground storage tank system are installed at an UST facility. The equipment necessary to connect the dispenser to the underground storage tank system includes check valves, shear valves, unburied risers or flexible connectors, or other transitional components that are beneath the dispenser and connect the dispenser to the underground piping.
2. Under-dispenser containment shall:
i. Be liquid-tight on its sides, bottom, and at any penetrations;
ii. Be compatible with the substance conveyed by the piping; and
iii. Allow for visual inspection and access to the components in the containment system, or be monitored for leaks from the dispenser system, in accordance with N.J.A.C. 7:14B-5.12(a)1 ii.

N.J. Admin. Code § 7:14B-4.1A

Adopted by 50 N.J.R. 409(a), effective 1/16/2018