N.J. Admin. Code § 7:10-12.6

Current through Register Vol. 56, No. 24, December 18, 2024
Section 7:10-12.6 - Water volume requirements
(a) The pumping capacity from all available water sources for a public noncommunity or nonpublic water system shall meet the following minimum requirements:
1. For water systems that supply residential consumers, the system shall deliver a minimum of 2.0 gallons per minute per bedroom served for 30 minutes.
2. For water systems that supply all persons other than residential consumers and use hydropneumatic storage, the pumping capacity shall be 10 times the average daily demand as determined using Table 1 below. If gravity storage is used, the minimum pumping capacity may be lowered, but not to less than the minimum required yield as set forth in (b) below.
(b) The total yield from all available water sources for a public noncommunity or nonpublic water system shall meet the following minimum requirements:
1. For water systems that supply residential realty improvements, the yield shall be at least 0.25 gallons per minute per bedroom served.
2. For water systems that supply all persons other than residential consumers, the yield shall be at least three times the average daily demand as determined using Table 1 below.

Click here to view image.

N.J. Admin. Code § 7:10-12.6

Amended by R.2004 d.442, effective 12/6/2004.
See: 36 N.J.R. 295(a), 36 N.J.R. 5383(b). Rewrote (b).