N.J. Admin. Code § 7:10-12.12

Current through Register Vol. 56, No. 24, December 18, 2024
Section 7:10-12.12 - Minimum distance requirements
(a) The minimum distances at which certain components of a public noncommunity or nonpublic water system shall be located away from sanitary sewer and septic systems, fuel storage tanks and other structures are set forth in N.J.A.C. 7:9D-2.
1. An administrative authority may require a greater distance than that required in N.J.A.C. 7:9D-2 between a well and a sewage system component where gravel, limestone, or fractured, creviced or fissured rock formations are expected to be encountered during drilling.
2. An administrative authority shall approve a reduction in the distance required between a well and a disposal field or a seepage pit to a minimum of 50 feet if the well is provided with a casing to a depth of 50 feet or more and such casing extends to, and is sealed into, a confining layer separating the aquifer into which the well is drilled from the stratum of soil in which the disposal field is located.
3. The administrative authority shall approve a reduction in the distance from a well to a building sewer to a minimum of 15 feet if it can be demonstrated that the building sewer is watertight and there are no other practicable alternatives.

N.J. Admin. Code § 7:10-12.12

Amended by R.2001 d.313, effective 9/4/2001 (operative October 4, 2001).
See: 32 New Jersey Register 2832(a), 33 New Jersey Register 3194(a).
Rewrote (a); deleted (b) through (e).