N.J. Admin. Code § 5:70-4.11

Current through Register Vol. 56, No. 23, December 2, 2024
Section 5:70-4.11 - Means of egress
(a) Every story utilized for human occupancy having an occupant load of 500 or less shall be provided with a minimum of two exits, except as provided in (b) below. Every story having an occupant load of 501 to 1,000 shall have a minimum of three exits. Every story having an occupant load of more than 1,000 shall have a minimum of four exits.
1. Each mezzanine with an occupant load of more than 50 or in which the travel distance to an exit exceeds 75 feet shall have access to at least two independent means of egress by November 6, 1990.
2. When more than one exit is required, an existing fire escape shall be accepted as providing one of the required means of egress unless judged to be dangerous for use under emergency exiting conditions.
i. Access to a fire escape shall be through a door, except that window access shall be permitted from single dwelling units or guestrooms in Use Groups R-1, R-2 and I-1 or when serving spaces having a maximum occupant load of 10 in other use groups.
(1) Exception: Window access shall be permitted to serve more than one guestroom for bed and breakfasts in Use Group R-1 provided that the window serves a floor with a maximum occupant load of 10 and that the window has a clear opening of at least 5.7 square feet, a minimum net clear opening of 24 inches in height, a minimum net clear opening of 20 inches in width, and a sill height of not more than 44 inches above the finished floor.
(2) For bed and breakfasts in Use Group R-1, where a door is required because the occupant load served exceeds 10, the door shall have a clear opening of at least 10 square feet, a minimum net clear opening of 54 inches in height and a minimum net clear opening of 24 inches in width.
3. Any new fire escapes shall be constructed and installed in accordance with the Uniform Construction Code Formal Technical Opinion No. FTO-3 dated June 2001.
i. Access to a fire escape shall be through a door installed in accordance with the Uniform Construction Code Formal Technical Opinion No. FTO-3 dated June 2001, except that window access shall be permitted from single dwelling units or guestrooms in Use Groups R-1, R-2 and I-1 or when serving spaces having a maximum occupant load of 10 in other use groups.
(1) Exception: Window access shall be permitted to serve more than one guestroom for bed and breakfasts in Use Group R-1 provided that the window serves a floor with a maximum occupant load of 10 and that the window has a clear opening of at least 5.7 square feet, a minimum net clear opening of 24 inches in height, a minimum net clear opening of 20 inches in width, and a sill height of not more than 44 inches above the finished floor.
(2) For bed and breakfasts in Use Group R-1, where a door is required because the occupant load served exceeds 10, the door shall have a clear opening of at least 10 square feet, a minimum net clear opening of 54 inches in height and a minimum net clear opening of 24 inches in width.
4. In all buildings of Use Group A, Use Group E, buildings of Use Group I, rooming houses, and child care centers, ladders of any type are prohibited on all new and existing fire escapes used as a required means of egress.
5. All occupants shall have unobstructed access to all new and existing fire escapes without having to pass through a room subject to locking.
6. In all bed and breakfast homestays, every sleeping room shall be provided with an approved window having sill height of not more than 44 inches.
7. In dwelling units in basements or stories below grade in buildings of Use Group R-2 that are not equipped throughout with an automatic fire sprinkler system, there shall be at least two exits from each dwelling unit.
i. An approved window providing a clear opening of at least five square feet in area, a minimum net clear opening of 24 inches in height and a minimum net clear opening of 20 inches in width, and a sill height of not more than 44 inches above the finished floor, shall be acceptable as one of the required exits.
(b) In buildings having only one exit, the single exit condition shall be permitted to continue as follows:
1. In buildings of Use Group R-3;
2. In all buildings, in the story at the level of exit discharge when the occupant load of the story does not exceed 50 and the exit access travel distance does not exceed 75 feet;
i. Exception to (b)2 above: In buildings of Use Group I and in rooming houses and child care centers, regardless of Use Group, two means of egress shall be required.
3. In buildings of Use Groups R-1 and R-2, not more than two stories in height, from floors that are not more than 16 feet above exterior grade, when there are not more than four dwelling units per floor and the exit access travel distance does not exceed 50 feet. The minimum fire resistance rating of the exit enclosure and of the opening protection shall be one hour.
i. In community residences for the developmentally disabled, the maximum occupant load, excluding staff, is 12.
4. In buildings of Use Group B or S-2, not more than two stories in height, which are not greater than 3000 square feet per floor, when the exit access travel distance does not exceed 75 feet. The minimum fire resistance rating of the exit enclosure and of the opening protection shall be one hour.
5. Open parking structures where vehicles are mechanically parked.
(c) In multi-level dwelling units in buildings of Use Groups R-1 or R-2, an exit shall not be required from each level of the dwelling unit provided that the following conditions are met:
1. The building in which such dwelling units are contained is of type 1 or type 2 construction and the travel distance within the dwelling unit does not exceed 75 feet; or
2. The building in which such dwelling units are contained is not more than three stories in height and all third floor space is part of one or more dwelling units located in part on the second floor and no habitable room within any such dwelling unit shall have a travel distance that exceeds 50 feet from the outside of the habitable room entrance door to the inside of the entrance door to the dwelling unit.
(d) All rooms and spaces having an occupant load greater than 50 or in which the travel distance exceeds 75 feet shall have a minimum of two egress doorways.
1. The following are exceptions to (d) above:
i. Storage rooms having a maximum occupant load of 10;
ii. Classrooms having a maximum occupant load of 75 in buildings equipped throughout with an automatic fire suppression system;
iii. In buildings of Use Group I-2, any patient sleeping room or suite of rooms greater than 1,000 square feet shall have a minimum of two egress doorways.
(e) When buildings of Use Groups A-2 and A-3 have more than two individual rooms which can be used for separate functions and each room has an occupant load of more than 300, the required egress doors from such rooms shall lead directly outside or to an exit passageway.
1. Such passageways shall be completely enclosed by assemblies having a fire-resistance rating of not less than two hours.
2. Such passageways shall not be used for any other purpose and shall lead directly outside.
(f) The capacity of means of egress in each story shall be sufficient for the occupant load thereof.
1. The capacity per unit of egress width shall be computed in accordance with the Table 5:70-4.11(f)1 for the specified use groups.

Table 5:70-4.11(f)1
CAPACITY PER UNIT EGRESS WIDTH
Without fire suppression system Number of occupantsWith fire suppression system Number of occupants
Use groupStairwaysDoors, Ramps and CorridorsStairwaysDoors, Ramps and Corridors
A75100113150
B6010090150
E75100113150
F6010090150
H----60100
I-16010090100
I-222303545
I-36010090150
M6010090150
R75100113150
S6010090150

2. The unit of egress width for all approved types of means of egress parts and facilities shall be 22 inches with a credit of one half unit for each 12 inches width in addition to one or more 22 inch units. Fractions of a unit of width less than 12 inches shall not be credited.
3. The maximum permitted occupant load of a given space shall be determined by dividing the floor area for a given use by the occupant load factor in Table 5:70-4.11(f)3.
i. Except in Use Group A-2 (nightclubs), the occupant load may be equal to the total number of occupants for whom exit capacity is provided as determined by (f)1 above. The resulting total occupant load shall not exceed one occupant per five square feet of net floor area over the entire use.

Table 5:70-4.11(f)3
Floor Area Per Occupant
UseOccupant Load Factor in square
feet per occupant
Assembly
Fixed seatingNote 1
Tables and chairs15 net
Chairs only7 net
Dance floors7 net
Standing space5 net
Waiting space (Note 2)3 net
Bowling centers
Lanes5 persons
Other areasper assembly above
Business100 gross
Educational
Fixed seatingNote 1
Classrooms20 net
Shops and vocational areas50 net
Industrial100 gross
Institutional
Inpatient treatment240 gross
Outpatient100 gross
Sleeping rooms120 gross
Library
Reading room50 net
Stack area100 gross
Mercantile
Grade floor or basement30 gross
All other floors60 gross
Storage, stock, shipping300 gross
Parking garages200 gross
Residential200 gross
Storage areas, mechanical equipment room300 gross

Note 1. The occupant load for that portion of an assembly area having fixed seats shall be determined by the number of fixed seats installed. Capacity of seats without dividing arms is one person per 18 inches. For booths, one seat equals 24 inches. One person is allowed for each fixed seat with dividing arms or fixed stand alone stool.

Note 2. Waiting space means that space in an assembly occupancy where persons are admitted to the building at times when seats are not available to them and are allowed to wait in a lobby or similar space until seats are available. Such use of the lobby or similar space shall not encroach upon the required clear width of exits.

(g) All buildings of Use Group A with an occupant load of 100 or more shall be provided with a main entrance capable of serving as the main exit with an egress capacity for at least one-half the total occupant load. The remaining exits shall be capable of providing two-thirds of the total required exit capacity.
1. For Use Group A-2 (nightclubs), the main exit and at least one remaining exit shall be placed a distance apart equal to one-half the length of the maximum overall diagonal distance of the area served in buildings not equipped throughout with an automatic fire sprinkler system and one-third the maximum overall diagonal distance of the area served in buildings or portions thereof that are equipped throughout with an automatic fire sprinkler system.
2. Use Group A-2 (nightclub) buildings or portions thereof with an occupant load of more than 300 shall have a main entrance capable of serving as the main exit with an egress capacity for at least two-thirds of the total occupant load. The remaining exits shall also be capable of providing two-thirds of the total required exit capacity.
(h) The length of a dead end corridor shall not exceed 35 feet.
1. The following are exceptions to (h) above:
i. The maximum length of a dead end corridor shall be 50 feet in buildings equipped throughout with an automatic fire alarm system installed in accordance with the New Jersey Uniform Construction Code.
ii. The maximum length of a dead end corridor shall be 70 feet in buildings equipped throughout with an automatic fire suppression system installed in accordance with the New Jersey Uniform Construction Code.
(i) All means of egress shall be provided with artificial illumination as follows:
1. All means of egress in other than buildings of Use Group R-3 shall be equipped with artificial lighting facilities to provide the intensity of illumination herein prescribed continuously during the time that conditions of occupancy of the building require that the exits be available. Lighting shall also be provided to illuminate the exit discharge in all buildings other than Use Groups F, H and S. In buildings of Use Group R-2, means of egress lighting, except that lighting within a dwelling unit, shall be wired on a circuit independent of circuits within any dwelling unit. The disconnecting means and overcurrent protection device shall not be located within a dwelling unit or such that access must be obtained by going through a dwelling unit.
2. The intensity of light at floor level shall be not less than one foot candle.
3. In buildings of Use Groups A and E used for the exhibition of motion pictures or other projections by means of directed light, and in buildings or spaces of Use Group A-1 or A-2 (nightclubs) used for performances, illumination may be reduced during periods of projection or performance to not less than 0.2 foot candle.
i. The lighting of exits, aisles, auditoriums and other assembly spaces shall be controlled from a location inaccessible to unauthorized persons. Supplementary control shall also be provided in the motion picture projection room or lighting booth, if any.
ii. In assembly spaces, illumination shall be restored automatically to the level required by (i)2 above upon activation of the fire suppression or fire alarm system.
(j) Means of egress lighting shall be connected to an emergency electrical system conforming to the adopted electrical subcode of the Uniform Construction Code in effect at the time of installation to assure continued illumination for a duration of not less than one hour in case of primary power loss in all buildings, rooms, or spaces required to have more than one exit or exit access.
(k) In all buildings, rooms, or spaces required to have more than one exit or exit access, all required means of egress shall be indicated with approved internally illuminated, externally illuminated, or self-luminous signs reading "Exit", visible from the exit access and, when necessary, supplemented by directional signs in the exit access indicating the direction and way of egress. All "Exit" signs shall be located at exit doors or exit access areas, so as to be readily visible.
1. Exceptions to (k) above:
i. Exit signs shall not be required in buildings of Use Groups I-1, R-2 and R-3 having a total occupant load, excluding staff, of 20 or less.
ii. Exit signs shall not be required when the second means of egress is a fire escape that is accessed directly from the individual sleeping rooms.
iii. Approved main exterior doors that are clearly identified as exits are not required to have "Exit" signs.
2. "Exit" signs shall have red or green letters at least six inches high and the minimum width of each stroke shall be three-quarter inch on a white background or in other approved distinguishable colors. If an arrow is provided as part of an "Exit" sign, the construction shall be such that the arrow direction cannot be readily changed. The word "Exit" shall be clearly discernible when the internally illuminated sign is not energized.
3. Each sign shall be illuminated by a source providing not less than five foot candles at the illuminated surface.
i. Exception to (k)3 above: Approved self-luminous signs which provide evenly illuminated letters shall have a minimum luminance of 0.06 foot lamberts.
4. All "Exit" signs shall be illuminated at all times when the building is occupied. To assure continued illumination for a duration of not less than one hour in case of primary power loss, the "Exit" signs shall be connected to an emergency electrical system.
i. Exception to (k)4 above: Approved self-luminous signs which provide continuous illumination independent of external power sources need not be connected to an emergency electrical system.
(l) Means of egress doors shall conform to the following:
1. All egress doors serving an occupant load greater than 50 shall swing in the direction of exit travel;
2. In building of Use Groups R-1 and R-2 all doors opening onto a passageway at grade or exit stair shall be self-closing and self-latching or automatic closing and self-latching listed closure devices.
3. All dwelling unit, guest room, or rooming unit corridor doors in buildings of Use Groups R-1, R-2, or I-1 shall be at least 1 3/8 inch solid core wood or approved equal with approved door closers, shall be self-latching and shall not have any glass panels, other than approved wire glass in metal frames. Corridor doors shall not be constructed of hollow core wood, shall not contain louvers and shall not be of panel construction. Doors shall fit both plumb and level in frames, and be reasonably tight fitting. All replacement doors shall be 1 3/4 inch solid core wood or approved equal, unless the existing frame will accommodate only a 1 3/8 inch door.
i. Existing doors meeting the requirements of Federal Housing and Urban Development Rehabilitation Guidelines Fire Rating of Archaic Materials and Assemblies or of Section 5 of Appendix B of the BOCA Basic/National Existing Structures Code, 1984 Ed. for a rating of 15 minutes or better shall be accepted as meeting the provisions of this requirement.
(1) Modifications made to existing doors to achieve the required rating shall be conducted in accordance with the Uniform Fire Code.
ii. Existing doors in buildings provided with approved, complete automatic suppression shall be required only to provide a smoke barrier; shall not contain louvers; shall fit plumb and level; and be reasonably tight fitting.
iii. In group homes with a maximum of 15 occupants, and which are protected with an approved automatic detection system, closing devices may be omitted.
4. Buildings of Use Group I-3 having remote power unlocking capability on more than 10 doors shall be provided with an emergency power source for such locks. Power shall be arranged to automatically operate upon failure of normal power within 10 seconds and for a duration of not less than one hour.
5. All required exit doors equipped with latching devices in buildings or portions thereof of Use Group A with an occupant load greater than 100 shall be equipped with approved panic hardware by November 6, 1990.
(m) Every required exit stairway having three or more risers and not provided with handrails or in which the existing handrails are judged to be in danger of collapsing when used under emergency exiting conditions, shall be provided with handrails for the full length of the run of steps on at least one side. All exit stairways more than 66 inches wide and subject to the maximum designed occupancy load shall have handrails on both sides. Where there are no handrails or where the existing handrails must be replaced in order to correct a hazardous condition, the handrails shall be designed and installed in accordance with the provisions of the New Jersey Uniform Construction Code.
(n) Every open portion of a stair, landing, or balcony which is more than 30 inches above the floor or grade below and not provided with guards or those in which the existing guards are judged to be in danger of collapsing when used under emergency exiting conditions, shall be provided with guards. Where there are no guards or where the existing guards must be replaced in order to correct a hazardous condition, the guards shall be designed and installed in accordance with the New Jersey Uniform Construction Code.
(o) In all buildings of Use Group R-1 and R-2 all transoms shall be either glazed with 1/4" wire glass set in metal frames and permanently secured in the closed position or sealed with materials consistent with the corridor construction. Any other sash, grill or opening in a corridor, and any window in a corridor not opening to the outside air, shall be sealed with materials consistent with the corridor construction.

N.J. Admin. Code § 5:70-4.11

Administrative change, 47 N.J.R. 648(a).
Amended by 50 N.J.R. 729(a), effective 2/5/2018