Section 12:90-6.3 - Relief devices
(a) A relief device of proper size shall be installed on the compressor discharge line, located between the compressor outlet port and the discharge shut-off valve. This relief device may discharge into the suction side.
(b) A relief device shall also be installed to relieve from the vapor space of the liquid receiver, condenser, and other pressure vessels in the system.
(c) Relief devices shall discharge to the atmosphere at a safe point and through a diffuser, except as provided in (a) above and (d) below.
(d) Where discharge to the atmosphere is impracticable or hazardous to the immediate neighborhood, the relief device may discharge into a receptacle through which the refrigerant can be disposed of in a safe manner.